Datasheet

https://www.phoenixcontact.com/us/produkte/2813509
Nov 14, 20132/5
Current transducers-MCR-SL-S-400-I-LP-2813509
Technical data
Switching output
Output name
No switching output
Power supply
Supply voltage range
20 V DC ... 30 V DC
Connection data
Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
14
Stripping length
8 mm
Screw thread
M3
General
Maximum transmission error
< 1 % (of final value)
Maximum temperature coefficient
< 0.025 %/K
Step response (10-90%)
< 340 ms
Surge voltage category
III
Pollution degree
2
Rated insulation voltage
300 V AC (to earth)
Test voltage input/output
5 kV (50 Hz, 1 min.)
Color
green
Housing material
Polyamide PA non-reinforced
Mounting position
Any
Conformance
CE-compliant
UL, USA / Canada
cULus
classifications
eCl@ss
eCl@ss 4.0
27200303
eCl@ss 4.1
27200303
eCl@ss 5.0
27200303
eCl@ss 5.1
27200303
eCl@ss 6.0
27200303
eCl@ss 7.0
27142316
eCl@ss 8.0
27142316
ETIM
ETIM 2.0
EC001440
ETIM 3.0
EC001440