Datasheet
https://www.phoenixcontact.com/us/produkte/2813486
Nov 13, 20132/5
Current transducers-MCR-SL-S-100-I-LP-2813486
Technical data
Input data
Connection method
Clamp-on cable design, diameter 18.5 mm
Output data
Output name
Current output
Current output signal
4 mA ... 20 mA
Max. output current
< 25 mA
Load/output load current output
((U
B
- 12 V) x 350 / 12 A)
Switching output
Output name
No switching output
Power supply
Supply voltage range
20 V DC ... 30 V DC
Connection data
Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
14
Stripping length
8 mm
Screw thread
M3
General
Maximum transmission error
< 1 % (of final value)
Maximum temperature coefficient
< 0.025 %/K
Step response (10-90%)
< 340 ms
Surge voltage category
III
Pollution degree
2
Rated insulation voltage
300 V AC (to earth)
Test voltage input/output
5 kV (50 Hz, 1 min.)
Color
green
Housing material
Polyamide PA non-reinforced
Mounting position
Any
Conformance
CE-compliant
UL, USA / Canada
cULus
classifications
eCl@ss
eCl@ss 4.0
27200303
eCl@ss 4.1
27200303