Datasheet
https://www.phoenixcontact.com/us/produkte/2811556
Nov 14, 20136/9
Signal conditioner-MACX MCR-UI-UI-SP-NC-2811556
Technical data
Safety characteristic data
MTBF
258 Years
λ
SU
3.16 x 10
-7
(316 FIT)
λ
SD
0
λ
DU
6.28 x 10
-8
(63 FIT)
λ
DD
0
Probability of a hazardous failure per hour (PFH
D
)
6,28 x 10
-8
Diagnostic coverage (DC)
0 %
Integrity requirement
IEC 61508 - High demand
Designation
Output isolator (live zero signals)
Architecture
Single-channel, 1oo1
Equipment type
Type A
Safety Integrity Level (SIL)
Up to 2
Safe Failure Fraction (SFF)
82.92 %
MTBF
258 Years
λ
SU
3.14 x 10
-7
(314 FIT)
λ
SD
0
λ
DU
6.48 x 10
-8
(65 FIT)
λ
DD
0
Probability of a hazardous failure per hour (PFH
D
)
6,48 x 10
-8
Diagnostic coverage (DC)
0 %
classifications
eCl@ss
eCl@ss 4.0
27210120
eCl@ss 4.1
27210120
eCl@ss 5.0
27210120
eCl@ss 5.1
27210120
eCl@ss 6.0
27210120
eCl@ss 7.0
27210120
eCl@ss 8.0
27210120
ETIM
ETIM 2.0
EC001485
ETIM 3.0
EC001485
ETIM 4.0
EC001485
ETIM 5.0
EC001485
UNSPSC
UNSPSC 6.01
30211506
UNSPSC 7.0901
39121008
UNSPSC 11
39121008