Signal conditioner-MACX MCR-UI-UI-SP-NC-2811556
Technical data
Output data
Voltage output signal
0 V ... 2.5 V
Voltage output signal
0.5 V ... 2.5 V
Voltage output signal
-2.5 V ... 2.5 V
Current output signal
0 mA ... 5 mA
Current output signal
0 mA ... 10 mA
Current output signal
0 mA ... 20 mA (please indicate if different setting when ordering)
Current output signal
1 mA ... 5 mA
Current output signal
2 mA ... 10 mA
Current output signal
4 mA ... 20 mA
Current output signal
-5 mA ... 5 mA
Current output signal
-10 mA ... 10 mA
Current output signal
-20 mA ... 20 mA
Load/output load voltage output
≥ 1 kΩ (10 V)
Load/output load current output
≤ 600 Ω (20 mA; active)
Load/output load current output
(passive: ≤ (UB-2 V) / I
outmax
)
Power supply
Supply voltage range
12 V DC ... 24 V DC (-20% / +25%)
Connection data
Connection method
Spring-cage conn.
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
1.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
1.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
16
Stripping length
8 mm
General
Maximum transmission error
≤ 0.1 % (Compared to the final value)
Maximum temperature coefficient
0.0075 %/K
Limit frequency (3 dB)
10 kHz (Can be switched to 30 Hz)
Alignment zero
± 4 %
Alignment span
± 4 %
Step response (10-90%)
35 µs (at 10 kHz)
Step response (10-90%)
11 ms (At 30 Hz)
Protective circuit
Transient protection
Surge voltage category
II
Pollution degree
2
Rated insulation voltage
300 V AC
Test voltage, input/output/supply
2.5 kV (50 Hz, 1 min.)
Color
green