Temperature measuring transducer-MACX MCR-T-UI-
UP-2811394
Technical data
Ambient conditions
Ambient temperature (storage/transport)
-40 °C ... 85 °C
Maximum altitude
≤ 2000 m
Permissible humidity (operation)
typ. 5 % ... 95 % (no condensation)
Noise immunity
EN 61000-6-2 When being exposed to interference, there may be
minimal deviations.
Input data
Sensor types (RTD) that can be used
Pt, Ni, Cu sensors: 2, 3, 4-wire
Sensor types that can be used (TC)
B, E, J, K, N, R, S, T, L, U, CA, DA, A1G, A2G, A3G, MG, LG
Temperature measuring range
-250 °C ... 2500 °C (Range depending on the sensor type)
Input signal range
0 Ω ... 50 kΩ
Potentiometer resistance range
0 Ω ... 50 kΩ
Input signal range
-1000 mV ... 1000 mV
Output data
Max. voltage output signal
± 11 V
Current output signal
4 mA ... 20 mA (in the case of SIL; further free configuration
without SIL)
Max. current output signal
22 mA
Load/output load voltage output
≥ 10 kΩ
Load/output load current output
≤ 600 Ω (20 mA)
Behavior in the event of a sensor error
According to NE 43 or freely configurable
Output name
Relay output
Contact type
1 PDT
Contact material
AgSnO
2
, hard gold-plated
Maximum switching voltage
30 V AC (30 V DC)
Maximum inrush current
0.5 A (30 V AC)
Maximum inrush current
1 A (30 V DC)
Power supply
Supply voltage range
24 V ... 230 V AC/DC (-20%/+10%, 50/60 Hz)
Power consumption
< 1.5 W
Connection data
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
14
Stripping length
7 mm
Screw thread
M3
Connection method
Screw connection