Voltage measuring transducers-MCR-VAC-UI-O-DC-2811103
Technical data
Input data
Input resistance
170 kΩ
Input voltage range
0 V ... 120 V AC
Input resistance
120 kΩ
Input voltage range
0 V ... 80 V AC
Input resistance
80 kΩ
Input voltage range
0 V ... 54 V AC
Input resistance
54 kΩ
Input voltage range
0 V ... 36 V AC
Input resistance
36 kΩ
Input voltage range
0 V ... 24 V AC
Input resistance
24 kΩ
Nom. voltage
440 V (ungrounded)
Nom. voltage
250 V (to earth)
Output data
Output name
Voltage output
Voltage output signal
0 V ... 10 V
Max. output voltage
15 V
Load/output load voltage output
> 10 kΩ
Output name
Current output
Current output signal
0 mA ... 20 mA
Current output signal
4 mA ... 20 mA
Max. output current
30 mA
Load/output load current output
< 500 Ω
Power supply
Supply voltage range
18.5 V DC ... 30.2 V DC
Max. current consumption
< 45 mA
Connection data
Connection method
Pluggable screw connection
Conductor cross section solid min.
0.2 mm²
Conductor cross section solid max.
2.5 mm²
Conductor cross section stranded min.
0.2 mm²
Conductor cross section stranded max.
2.5 mm²
Conductor cross section AWG/kcmil min.
24
Conductor cross section AWG/kcmil max
14
Stripping length
8 mm
Screw thread
M3
General
Maximum transmission error
< 1.5 % (of final value)
Temperature coefficient, typical
0.02 %/K (50/60 Hz)
Frequency measuring range
45 Hz ... 400 Hz