Datasheet
https://www.phoenixcontact.com/de/products/2800904
04/05/2017Page2/9
Electronic device circuit breaker-CB E1 24DC/4A NO P-2800904
Technical data
Dimensions
Complete module width 12.3 mm
Complete module depth 77.3 mm
Ambient conditions
Ambient temperature (operation) -25 °C ... 50 °C (non-condensing)
Ambient temperature (storage/transport) -40 °C ... 70 °C
Humidity test 96 h, 95% RH, 40°C
Degree of protection IP30 (Actuation area)
General
Installation instructions
When mounted in rows without convection cooling, the nominal device
current should only be led to a maximum of 80% due to the thermal
effect during continuous operation (100% operating factor).
Special precautionary measures must be taken in systems or machines,
to prevent components from restarting (e.g., use of a safety PLC).
Parallel connection of multiple circuit breakers is not permitted.
Flammability rating according to UL 94 V0
Mounting type On base element
Color gray
Number of positions 1
Degree of pollution 2
Design Male
Electrical data
Fuse type Electronic
Rated surge voltage 0.5 kV
Operating voltage 24 V DC
18 V DC ... 30 V DC
Nominal current I
N
4 A
Required backup fuse not required, integrated failsafe element
Active current limitation
typ. 1.25 x I
N
Closed circuit current I
0
typ. 8 mA (When switched on)
typ. 17 mA (With alarm output)
Power dissipation 0.81 W (Nominal operation)
Temperature derating 4 A (at50°C)
Tripping method E (electronic)
Dielectric strength max. 30 V DC (Load circuit)
Voltage drop
100 mV (at I
N
)
Contact type without electrical isolation
Shutdown time load circuit 200 ms (see time/current characteristic curve)
Undervoltage shutdown load circuit < 14 V (typ. OFF)
> 17 V (typ. ON)
Max. capacitive load load circuit 20000 µF
Auxiliary type of contact floating signal contact