Datasheet

https://www.phoenixcontact.com/us/produkte/2736699
Nov 14, 20132/6
Power supply unit-ASI QUINT 100-240/4.8 EFD-2736699
Technical data
Input data
Nominal input voltage range
100 V AC ... 240 V AC
Input voltage range AC
85 V AC ... 264 V AC
Input voltage range DC
90 V DC ... 350 V DC
AC frequency range
45 Hz ... 65 Hz
Frequency range DC
0 Hz
Current consumption
approx. 1.8 A (120 V AC)
Current consumption
1 A (230 V AC)
Nominal power consumption
144 W
Inrush surge current
< 15 A (typical)
Power failure bypass
> 60 ms (120 V AC)
Power failure bypass
> 100 ms (230 V AC)
Input fuse
5 A (slow-blow, internal)
Output data
Nominal output voltage
30.1 V DC ±1,5 %
Output current
4.8 A (Up to +60°C)
Output current
6 A
Connection in parallel
No
Connection in series
Yes
Residual ripple
< 30 mV
PP
Peak switching voltages nominal load
< 50 mV
PP
Maximum power dissipation NO-Load
4 W
Power loss nominal load max.
16 W
General
Net weight
0.9 kg
Operating voltage display
LED
Efficiency
> 89 % (for 230 V AC and nominal values)
Insulation voltage input/output
4 kV AC (type test)
Insulation voltage input/output
2 kV AC (routine test)
Protection class
I, IEC 61140, EN 61140, VDE 0140-1
MTBF (IEC 61709, SN 29500)
> 500000 h
Mounting position
horizontal DIN rail NS 35, EN 60715
Assembly instructions
Can be aligned: Horizontally 0 mm, vertically 50 mm
Electromagnetic compatibility
Conformance with EMC Directive 2004/108/EC
Low Voltage Directive
Conformance with LV directive 2006/95/EC
Standard - Safety of transformers
EN 61558-2-17
Standard - Electrical safety
EN 60950-1/VDE 0805 (SELV)
Standard - Electrical safety
DIN VDE 0100-410
Standard – Electronic equipment for use in electrical power
installations and their assembly into electrical power
installations
EN 50178/VDE 0160 (PELV)
Standard - Safe isolation
DIN VDE 0100-410