Datasheet
https://www.phoenixcontact.com/us/produkte/2736369
Nov 13, 20132/13
Distributed I/O device-FLM DIO 4/4 M12-2A-2736369
Technical data
General
Test section
To I/O 500 V AC
Interfaces
Name
Fieldline local bus
Connection method
M12 connector, B-coded
Designation connection point
Copper cable
Transmission speed
500 kBit/s / 2 MBit/s
Number of positions
5
Power supply for module electronics
Connection method
M12 connector
Name
U
L
Supply voltage
24 V DC
Supply voltage range
18 V DC ... 30 V DC IEC 61131-2 (including ripple)
Fieldline potentials
Voltage supply U
L
24 V DC
Power supply at U
L
max. 4 A
Current consumption from U
L
max. 50 mA (At 2 Mbaud)
Current consumption from U
L
typ. 45 mA (At 2 Mbaud)
Current consumption from U
L
max. 50 mA (At 500 kBaud)
Current consumption from U
L
typ. 40 mA (At 500 kBaud)
Voltage supply U
S
24 V DC
Power supply at U
S
max. 4 A
Current consumption from U
S
typ. 5 mA (plus power supply for sensors)
Current consumption from U
S
max. 600 mA
Voltage supply U
A11
24 V DC
Power supply at U
A11
max. 4 A
Current consumption at U
A11
typ. 3 mA
Current consumption at U
A11
max. 4 A
Voltage supply U
A12
24 V DC
Power supply at U
A12
max. 4 A
Current consumption at U
A12
typ. 3 mA
Current consumption at U
A12
max. 4 A
Digital inputs
Input name
Digital inputs
Connection method
M12 connector
Connection method
2, 3, 4-wire
Number of inputs
4
Protective circuit
Protection against polarity reversal
Filter time
3 ms
Input characteristic curve
IEC 61131-2 type 1