Pylontech Battery Guide

www.phocos.com 3 | P a g e
3.
Dip Switches location (see note below table for US2000C/US3000C*)
Locate the four battery Dip switches as shown above at position (position may vary on different battery
rack models). Each switch can be set ON in the top position or OFF in the bottom position*. Set the Dip
switches as follows, depending on the number of battery clusters / groups:
Dip 1 Dip 2 Dip 3 Dip 4 Group address
ON
RS-485
baud
rate =
9600
OFF OFF OFF
All models: Single group only. The master battery rack must have this
setting. Slave battery racks should have all Dip switches set to OFF.
Only C models: Two-group configuration. The master battery rack in
each group must have this setting. Slave battery racks should have
all Dip switches set to OFF.
ON OFF OFF
Only non-C models: Two-group configuration. The master battery
rack in the first group must have this setting. Slave battery racks
should have all Dip switches set to OFF.
OFF ON OFF
Only non-C models: Two-group configuration. The master battery
rack in the second group must have this setting. Slave battery racks
should have all Dip switches set to OFF.
* US2000C and US3000C batteries have their Dip switches mounted upside-down. So, while the table
and settings above are valid, each switch’s top position is OFF and the bottom position is ON. In this
example Dip 1 is in the ON position and all others are set to the OFF position:
4. Ensure the battery racks are still turned off. Connect the Any-Grid(s) to the battery power (positive and
negative) terminals with the correct polarity.
CAUTION: If the correct polarity of the battery is not observed, the Any-Grid and the battery may be
damaged, this is not covered by warranty.
5. If you are using the PSW-H-BAT-CABLE-PYLON-2 cable, it is marked with a “PYLON” label on one of the two
sides:
Connect this side to the master battery racks “RS485” port (for C models use the “B/RS485” port) and the
other side into the Any-Grid display panel’s “BMS” port.
If instead you are using the PSW-H-BAT-CABLE-PYLON, it is not labelled on either side. For this cable it does
not matter which orientation you choose, as it functions in both orientations (do not use for C models):