Phocos Any-Grid™ series Any-Grid™ use with Lithium battery models: Shoto SDA10-48100 Applicable for Any-Grid™ PSW-H-8kW-230/48V, PSW-H-5kW-230/48V, PSW-H-5kW-120/48V and PSW-H-6.
1.0 Introduction This guide outlines the recommended settings and establishing communication for operation of one or more AnyGrid™ PSW-H-8kW-230/48V, PSW-H-5kW-230/48V, PSW-H-5kW-120/48V or PSW-H-6.5kW-120/48V hybrid inverter chargers with Shoto SDA10-48100 battery modules in the low-voltage (48 Vdc nominal) configuration, referred to in this guide as “battery modules”. Note that the charge/discharge settings are automatically negotiated with the battery if this guide is used and cannot be changed.
.0 System Overview Shoto batteries 4.0 Battery Sizing To maintain the full battery warranty, each battery module should be sized not to exceed 50 Adc continuous current (verify Shoto manual for details). It is thus recommended to use at least 2 battery modules in parallel to deliver both sufficient continuous current and peak current for a single PSW-H-5KW at full power. When using multiple Any-Grid units, be sure to increase the number of batteries accordingly to sustain the required currents.
Any-Grid Battery 4. Ensure the battery modules are wired as outlined in the Shoto battery manual. Turn on the batteries: 5. Ensure the “ON/OFF” load power button of the Any-Grid(s) is in the ON position (depressed), but no loads are connected: The Any-Grid(s) should now be running, the display(s) on. 6. Apply the following setting on the Any-Grid to which the Shoto battery bank is connected with the communication cable.
The content of this document is subject to change without notice. Copyright © 2022 Phocos AG, all rights reserved. Version: 20220211 Phocos AG Magirus-Deutz-Str. 12 89077 Ulm, Germany Phone +49 731 9380688-0 Fax +49 731 9380688-50 www.phocos.com info@phocos.com www.phocos.