Protective Devices
Short Circuit Selectivity PL6 towards D01-D03 fuse link
Short circuit selectivity characteristic B towards fuse link D01-D03*)
PL6 D01-D03 gL/gG
I
n
[A]1016202535506380100
2 <0.5
1)
<0.5
1)
0.6 1.0 6.0
2)
6.0
2)
6.0
2)
6.0
2)
6.0
2)
4 <0.5
1)
<0.5
1)
0.5 0.9 2.5 6.0
2)
6.0
2)
6.0
2)
6.0
2)
5 <0.5
1)
0.5 0.8 1.7 4.0 6.0
2)
6.0
2)
6.0
2)
6 <0.5
1)
0.5 0.8 1.6 3.6 6.0
2)
6.0
2)
6.0
2)
8 0.5 0.8 1.4 2.8 4.3 6.0
2)
6.0
2)
10 0.5 0.7 1.3 2.4 3.4 6.0
2)
6.0
2)
13 <0.5
1)
0.7 1.2 2.3 3.2 5.3 6.0
2)
16 0.6 1.1 2.2 2.9 4.6 6.0
2)
20 1.1 2.1 2.8 4.4 6.0
2)
25 1.1 2.0 2.7 4.2 6.0
2)
32 2.0 2.6 4.0 6.0
2)
40 2.5 3.8 6.0
2)
50 2.3 3.4 6.0
2)
63 6.0
2)
Short circuit selectivity characteristic C towards fuse link D01-D03*)
PL6 D01-D03 gL/gG
I
n
[A] 10 16 20 25 35 50 63 80 100
2 <0.5
1)
<0.5
1)
0.5 0.7 6.0
2)
6.0
2)
6.0
2)
6.0
2)
6.0
2)
4 <0.5
1)
<0.5
1)
<0.5
1)
0.6 1.6 4.0 6.0
2)
6.0
2)
6.0
2)
5 <0.5
1)
<0.5
1)
0.5 1.3 3.1 5.7 6.0
2)
6.0
2)
6 <0.5
1)
<0.5
1)
<0.5
1)
1.2 2.7 4.5 6.0
2)
6.0
2)
8 <0.5
1)
<0.5
1)
<0.5
1)
1.2 2.5 4.0 6.0
2)
6.0
2)
10 <0.5
1)
<0.5
1)
1.2 2.3 3.1 5.4 6.0
2)
13 1.1 2.2 3.0 4.9 6.0
2)
16 1.1 2.1 2.8 4.4 6.0
2)
20 1.0 2.0 2.6 4.0 6.0
2)
25 1.9 2.5 3.8 6.0
2)
32 2.5 3.7 6.0
2)
40 3.5 6.0
2)
50 6.0
2)
Short circuit selectivity characteristic D towards fuse link D01-D03*)
PL6 D01-D03 gL/gG
I
n
[A]1016202535506380100
2 <0.5
1)
<0.5
1)
0.6 0.8 2.2 6.0
2)
6.0
2)
6.0
2)
6.0
2)
4 <0.5
1)
0.5 0.7 1.7 4.6 6.0
2)
6.0
2)
6.0
2)
5 <0.5
1)
<0.5
1)
0.6 1.5 3.5 5.8 6.0
2)
6.0
2)
6 <0.5
1)
0.5 1.3 2.9 4.5 6.0
2)
6.0
2)
8 <0.5
1)
0.5 1.2 2.4 3.5 6.0
2)
6.0
2)
10 0.5 1.1 2.2 3.0 5.0 6.0
2)
13 1.1 2.1 2.9 4.6 6.0
2)
16 1.9 2.6 3.9 6.0
2)
20 1.7 2.3 3.5 6.0
2)
25 2.2 3.4 6.0
2)
32 2.9 6.0
2)
40 5.7
In case of short circuit, there is selectivity between the miniature circuit breakers PL6 and the upstream fuses up to the specified values of the selectivity limit
current I
s
[kA] (i. e. in case of short-circuit currents I
ks
under I
s
, only the MCB will trip, in case of short circuit currents above this value both protective devices
will respond).
*) basically in accordance with EN 60898-1 D.5.2.b
1)
Selectivity limit current I
s
under 0.5 kA
2)
Selectivity limit current I
s
= rated breaking capacity I
cn
of the MCB
no selectivity