Technical data
9
Protective Devices
Residual Current Devices PF6
• Twin-purpose terminal (lift/open-mouthed) above and below
• Busbar positioning optionally above or below
• Free terminal space despite installed busbar
• Universal tripping signal switch, also suitable for PLS., PKN., Z-A. can be
mounted subsequently
• Auxiliary switch Z-HK can be mounted subsequently
• Contact position indicator red - green
• Suitable for being used with standard fluorescent tubes with or without
electronical ballast (typically up to 20 units per phase conductor)
• The device functions irrespective of the position of installation
• Mains connection at either side
• The 4-pole device can also be used for 3-pole connection.
For this purpose use terminals 1-2, 3-4, and 5-6 (+ cable link).
• The 4-pole device can also be used for 2-pole connection.
For this purpose use terminals 5-6 and N-N.
• The test key “T” must be pressed every month. The system operator must
be informed of this obligation and his responsibility in a way that can be
proven (self-adhesive RCD-label enclosed)
• Pressing the test key “T” serves the only purpose of function testing the
residual current device (RCD). This test does not make earthing resistance
measurement (R
E
), or proper checking of the earth conductor condition
redundant, which must be performed separately.
Accessories:
Auxiliary switch for
subsequent installation to the left Z-HK 248432
Tripping signal contact for
subsequent installation to the right Z-NHK 248434
Remote control and
automatic switching device Z-FW/LP 248296
Compact enclosure KLV-TC-2 276240
KLV-TC-4 276241
Sealing cover set Z-RC/AK-2TE 285385
Z-RC/AK-4TE 101062
Switching interlock IS/SPE-1TE 101911
Technical Data
Electrical
Design according to IEC/EN 61008
Current test marks as printed onto the device
Tripping instantaneous
Rated voltage U
n
230/400 V, 50 Hz
Rated tripping current I
Δn
30, 300 mA
Sensitivity AC and pulsating DC
Rated insulation voltage U
i
440 V
Rated impulse withstand voltage U
imp
4 kV
Rated short circuit strength I
nc
6 kA
Maximum back-up fuse Overload Short circuit
I
n
= 25-40 A 25 A gG/gL 63 A gG/gL
I
n
= 63 A 40 A gG/gL 63 A gG/gL
Rated breaking capacity I
m
or
Rated fault breaking capacity I
Δm
I
n
= 16-40 A 500 A
I
n
= 63 A 630 A
Voltage range of test button 2-pole 184 - 250 V~
4-pole 184 - 440 V~
Endurance
electrical comp. ≥ 4,000 operating cycles
mechanical comp. ≥ 20,000 operating cycles
Mechanical
Frame size 45 mm
Device height 80 mm
Device width 35 mm (2MU),
70 mm (4MU)
Mounting quick fastening with
2 lock-in positions on
DIN rail IEC/EN 60715
Degree of protection, built-in IP40
Deg. of prot. in moisture-proof encl. IP54
Upper and lower terminals open mouthed/lift terminals
Terminal protection finger and hand touch safe,
BGV A3, ÖVE-EN 6
Terminal capacity 1x (1.5 - 35) mm
2
single wire
2x (1.5 - 16) mm
2
multi wire
Busbar thickness 0.8 - 2 mm
Tripping temperature -25°C to +40°C
Storage- and transport temperature -35°C to +60°C
Resistance to climatic conditions 25-55°C/90-95% relative
humidity acc. to IEC 60068-2
Connection diagrams
2-pole 4-pole
15
26
T
3N
4N
Influence of the ambient temperature to the maximum continuous current (A)
25A 40A 63A
Ambient temperature
2p 4p 2p 4p 4p
40° 25 25 40 40 63
45° 21 22 37 37 59
50° 18 19 33 34 55
55° 14 16 30 31 50
60° –
*)
–
*)
26 27 45
Annotation: It has to be ensured that the values in the table are not exceeded and the back-up fuse/thermal protection works properly
*) not applicable
Dimensions (mm)
35
4580
10,5
4,530,5
44
60
5,5
2P
70
80
4P
RCD PF6 in a Three-Phase AC Network without Neutral Conductor
The N-terminal must be connected by a cable link
with the phase L2 (or L1), so that the test loop is
supplied with current and the RCD is tested cor-
rectly.
L1 L2 L3
L1 L2 L3