Technical data

72
Short Circuit Selectivity PLSM towards DII-DIV fuse link
In case of short circuit, there is selectivity between the miniature circuit breakers PLSM and the upstream fuses up to the specified values of the selectivity limit
current I
s
[kA] (i. e. in case of short-circuit currents I
ks
under I
s
, only the MCB will trip, in case of short circuit currents above this value both protective devices
will respond).
*) basically in accordance with EN 60898-1 D.5.2.b
Short circuit selectivity characteristic B towards fuse link DII-DIV*)
PLSM DII-DIV gL/gG
I
n
[A] 10 16 20 25 35 50 63 80 100
1.0 <0.5
1)
1.2 10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
1.5 <0.5
1)
1.0 10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
2.0 <0.5
1)
<0.5
1)
0.8 1.6 10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
2.5 <0.5
1)
<0.5
1)
0.8 1.5 10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
3.0 <0.5
1)
<0.5
1)
0.8 1.4 10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
3.5 <0.5
1)
<0.5
1)
0.7 1.3 10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
4 <0.5
1)
<0.5
1)
0.6 1.0 3.6 10.0
2)
10.0
2)
10.0
2)
10.0
2)
5 <0.5
1)
<0.5
1)
0.6 0.9 2.0 3.5 8.5 10.0
2)
10.0
2)
6 <0.5
1)
0.6 0.9 1.8 3.2 7.4 10.0
2)
10.0
2)
8 <0.5
1)
0.5 0.8 1.6 2.6 5.2 8.3 10.0
2)
10 0.5 0.8 1.4 2.2 3.9 6.0 10.0
2)
13 0.5 0.7 1.3 2.0 3.6 5.4 10.0
2)
16 0.6 1.2 1.9 3.2 4.6 8.4
20 1.2 1.8 3.1 4.4 7.8
25 1.2 1.8 3.0 4.2 7.3
32 1.7 2.8 3.9 6.8
40 2.7 3.8 6.5
50 2.5 3.5 5.7
63 5.3
Short circuit selectivity characteristic C towards fuse link DII-DIV*)
PLSM DII-DIV gL/gG
I
n
[A] 10 16 20 25 35 50 63 80 100
0.75 1.0 10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
1.0 <0.5
1)
1.2 10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
1.5 <0.5
1)
<0.5
1)
1.0 2.2 10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
2.0 <0.5
1)
<0.5
1)
0.8 1.6 10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
2.5 <0.5
1)
<0.5
1)
0.8 1.4 10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
3.0 <0.5
1)
<0.5
1)
0.8 0.9 10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
3.5 <0.5
1)
<0.5
1)
0.6 0.9 2.2 4.5 10.0
2)
10.0
2)
10.0
2)
4 <0.5
1)
<0.5
1)
0.6 0.8 1.8 3.6 9.7 10.0
2)
10.0
2)
5 <0.5
1)
<0.5
1)
0.6 0.7 1.5 2.7 7.3 10.0
2)
10.0
2)
6 <0.5
1)
0.5 0.6 1.4 2.4 5.5 10.0
2)
10.0
2)
8 <0.5
1)
<0.5
1)
0.6 1.3 2.2 4.7 8.7 10.0
2)
10 <0.5
1)
0.6 1.3 2.0 3.6 5.4 10.0
2)
13 1.3 1.9 3.3 5.0 9.4
16 1.2 1.8 3.2 4.4 8.0
20 1.2 1.8 3.1 4.1 7.0
25 1.7 2.8 3.8 6.5
32 2.7 3.7 6.2
40 3.5 5.9
50 5.5
63
1)
Selectivity limit current I
s
under 0.5 kA
2)
Selectivity limit current I
s
= rated breaking capacity I
cn
of the MCB
no selectivity
Short circuit selectivity characteristic D towards fuse link DII-DIV*)
PLSM DII-DIV gL/gG
I
n
[A] 10 16 20 25 35 50 63 80 100
0.5 0.5 3.0 10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
1.0 <0.5
1)
<0.5
1)
1.0 2.4 10.0
2)
10.0
2)
10.0
2)
10.0
2)
10.0
2)
1.5 <0.5
1)
<0.5
1)
0.7 1.2 3.5 7.7 10.0
2)
10.0
2)
10.0
2)
2.0 <0.5
1)
<0.5
1)
0.6 1.0 2.8 5.8 10.0
2)
10.0
2)
10.0
2)
2.5 <0.5
1)
<0.5
1)
0.6 1.4 2.3 4.6 10.0
2)
10.0
2)
10.0
2)
3.0 <0.5
1)
<0.5
1)
0.6 0.9 2.3 4.3 10.0
2)
10.0
2)
10.0
2)
3.5 <0.5
1)
<0.5
1)
0.6 0.9 2.1 4.0 10.0
2)
10.0
2)
10.0
2)
4 <0.5
1)
0.6 0.9 2.0 3.8 9.5 10.0
2)
10.0
2)
5 <0.5
1)
0.5 0.7 1.7 3.1 7.0 10.0
2)
10.0
2)
6 0.5 0.7 1.5 2.6 5.3 9.1 10.0
2)
8 <0.5
1)
0.7 1.4 2.2 3.9 6.0 10.0
2)
10 0.7 1.2 1.9 3.4 5.0 9.5
13 1.2 1.8 3.2 4.6 8.6
16 1.6 2.7 4.0 7.4
20 1.5 2.5 3.5 6.7
25 2.4 3.4 6.2
32 2.8 5.0
40 4.8
Protective Devices