Technical data
7
Protective Devices
Residual Current Devices PF7
• Residual current devices
• Shape compatible with and suitable for standard busbar connection to
other devices of the P-series
• Twin-purpose terminal (lift/open-mouthed) above and below
• Busbar positioning optionally above or below
• Free terminal space despite installed busbar
• Universal tripping signal switch, also suitable for PL., PFL., Z-A. can be
mounted subsequently
• Auxiliary switch Z-HK can be mounted subsequently
• Contact position indicator red - green
• Delayed types suitable for being used with standard fluorescent tubes with
or without electronical ballast (30mA-RCD: 30 units per phase conductor,
100mA-RCD: 90 units per phase conductor)
Notes: Depending of the fluorescent lamp ballast manufacturer partly more
possible. Symmetrical allocation of the fluorescent lamp ballasts on all
phases favourably. Shifting references of the fluorescent lamp ballast man-
ufacturer consider.
• The device functions irrespective of the position of installation
• Tripping is line voltage-independent. Consequently, the RCD is suitable for
“fault current/residual current protection” and “additional protection” with-
in the the meaning of the applicable installation rules
• Mains connection at either side
• Types with 80 a 100 A permissible short-circuit back-up fuse (PF7-80,
PF7-100): Take into account overload protection
• The 4-pole device can also be used for 3-pole connection.
For this purpose use terminals 1-2, 3-4, and 5-6 (+ cable link).
• The 4-pole device can also be used for 2-pole connection.
For this purpose use terminals 5-6 and N-N.
• The test key “T” must be pressed every month. The system operator must
be informed of this obligation and his responsibility in a way that can be
proven (self-adhesive RCD-label enclosed)
• Pressing the test key “T” serves the only purpose of function testing the
residual current device (RCD). This test does not make earthing resistance
measurement (R
E
), or proper checking of the earth conductor condition
redundant, which must be performed separately.
• Type -A: Protects against special forms of residual pulsating DC which
have have not been smoothed
• Type -G: High reliability against unwanted tripping. Compulsory for any cir-
cuit where personal injury or damage to property may occur in case of
unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6).
• Type -G/A: Additionally protects against special forms of residual pulsating
DC which have not been smoothed.
Special types for X-ray application PF7-...-R
• Type -S: Selective residual current device sensitive to AC, type -S.
Compulsory for systems with surge arresters downstream of the RCD
(ÖVE/ÖNORM E 8001-1 § 12.1.5).
• Type -S/A: Additionally protects against special forms of residual pulsating
pulsating DC which have not been smoothed.
Accessories:
Auxiliary switch for
subsequent installation to the left Z-HK 248432
Tripping signal contact for
subsequent installation to the right Z-NHK 248434
Remote control and
automatic switching device Z-FW/LP 248296
Compact enclosure KLV-TC-2 276240
KLV-TC-4 276241
Sealing cover set Z-RC/AK-2TE 285385
Z-RC/AK-4TE 101062
Switching interlock IS/SPE-1TE 101911
Technical Data
Electrical
Design according to IEC/EN 61008
Type G acc. to ÖVE E 8601
Current test marks as printed onto the device
Tripping instantaneous
Type G 10 ms delay
Type S 40 ms delay -
with selective disconnecting
function
Rated voltage U
n
230/400 V, 50 Hz
Rated tripping current I
Δn
10, 30, 100, 300, 500 mA
Sensitivity AC and pulsating DC
Rated insulation voltage U
i
440 V
Rated impulse withstand voltage U
imp
4 kV
Rated short circuit strength I
nc
10 kA
Maximum back-up fuse Overload Short circuit
I
n
= 16-40 A 25 A gG/gL 63 A gG/gL
I
n
= 63 A 40 A gG/gL 63 A gG/gL
I
n
= 80 A 50 A gG/gL 80 A gG/gL
I
n
= 100 A 63 A gG/gL 100 A gG/gL
Rated breaking capacity I
m
or
Rated fault breaking capacity I
Δm
I
n
= 16-40 A 500 A
I
n
= 63 A 630 A
I
n
= 80 A 800 A
I
n
= 100 A 1,000 A
Voltage range of test button 2-pole 184 - 250 V~
4-pole 184 - 440 V~
Endurance
electrical comp. ≥ 4,000 operating cycles
mechanical comp. ≥ 20,000 operating cycles
Mechanical
Frame size 45 mm
Device height 80 mm
Device width 35 mm (2MU),
70 mm (4MU)
Mounting quick fastening with
2 lock-in positions on
DIN rail IEC/EN 60715
Degree of protection, built-in IP40
Deg. of prot. in moisture-proof encl. IP54
Upper and lower terminals open mouthed/lift terminals
Terminal protection finger and hand touch safe,
BGV A3, ÖVE-EN 6
Terminal capacity 1x (1.5 - 35) mm
2
single wire
2x (1.5 - 16) mm
2
multi wire
Busbar thickness 0.8 - 2 mm
Tripping temperature -25°C to +40°C
Storage- and transport temperature -35°C to +60°C
Resistance to climatic conditions 25-55°C/90-95% relative
humidity acc. to IEC 60068-2
Connection diagrams
2-pole 4-pole
15
26
T
3N
4N