Protective Devices
Electronic Combined RCD/MCB Devices eRBM, 1+N-pole, 1 Module Unit
Electronic residual current device / miniature circuit breaker combination in
only 1MU
Tripping line voltage dependent
Contact position indicator red - green
Can be sealed with leads in the on and off position
Colour coded switching toggle (designating the rated current)
Permanently connected neutral conductor (950 mm long, blue)
Special application in British-Standard-Distibution Boxes
Can be connected to standard busbar (at the lower side)
Comprehensive range of accessories suitable for subsequent installation
Accessories:
Auxiliary switch for
subsequent installation Z-AHK 248433
Tripping signal switch for
subsequent installation Z-NHK 248434
Shunt trip release Z-ASA/.. 248286, 248287
Tripping module Z-KAM 248294
Technical Data
Electrical
Design according to BS/EN 61009
Current test marks as printed onto the device
Number of poles 1+N-pole
Pole switched,
N led through (solid neutral)
Rated voltage U
n
240 VAC
Rated frequency 50/60 Hz
Rated current I
n
6 - 45 A
Rated tripping current I
Δn
10, 30, 100, 300 mA
Sensitivity pulsating DC
Tripping Characteristic RCD component:
Tripping
line voltage-dependent instantaneous
Peak withstand current 250A (8/20µs)
Rated non-tripping current I
Δno
0.5 I
Δn
Voltage range for protective function 184 - 264 V~
Tripping Characteristic MCB component
Conventional non-tripping current 1.13 I
n
Conventional tripping current 1.45 I
n
Reference temperature 30°C
Characteristic B, C
Rated breaking capacity
10 kA
Selectivity class 3
Maximum back-up fuse > 6 kA 100 A gL
Endurance electrical comp. 4,000 operating cycles
mechanical comp. 20,000 operating cycles
Mechanical
Frame size 45 mm
Device height 102.6 mm
Device width 17.7 mm (1MU)
Mounting quick fastening with
2 lock-in positions on
DIN rail IEC/EN 60715
Upper terminals lift terminals
Lower terminals open mouthed/lift terminals
Terminal protection finger and hand touch safe,
BGV A3, ÖVE-EN 6
Terminal capacity 1 - 25 mm
2
Busbar thickness below 0.8 - 2 mm
Degree of protection, built-in IP40
Perm. ambient temperature range -25°C to +40°C
Resistance to climatic conditions 25-55°C/90-95% relative
humidity acc. to IEC 60068-2
Dimensions (mm)
Connection diagram
1+N-pole