Technical data

5
Residual Current Devices PFIM
Residual current devices
Shape compatible with and suitable for standard busbar connection to
other devices of the P-series
Twin-purpose terminal (lift/open-mouthed) above and below
Busbar positioning optionally above or below
Free terminal space despite installed busbar
Universal tripping signal switch, also suitable for PLS., PKN., Z-A. can be
mounted subsequently
Auxiliary switch Z-HK can be mounted subsequently
Contact position indicator red - green
Delayed types suitable for being used with standard fluorescent tubes with
or without electronical ballast (30mA-RCD: 30 units per phase conductor,
100mA-RCD: 90 units per phase conductor)
Notes: Depending of the fluorescent lamp ballast manufacturer partly more
possible. Symmetrical allocation of the fluorescent lamp ballasts on all
phases favourably. Shifting references of the fluorescent lamp ballast man-
ufacturer consider.
The device functions irrespective of the position of installation
Tripping is line voltage-independent. Consequently, the RCD is suitable for
“fault current/residual current protection” and “additional protection” with-
in the the meaning of the applicable installation rules
Mains connection at either side
The 4-pole device can also be used for 3-pole connection.
For this purpose use terminals 1-2, 3-4, and 5-6 (+ cable link).
The 4-pole device can also be used for 2-pole connection.
For this purpose use terminals 5-6 and N-N.
The test key “T” must be pressed every month. The system operator must
be informed of this obligation and his responsibility in a way that can be
proven (self-adhesive RCD-label enclosed)
Pressing the test key “T” serves the only purpose of function testing the
residual current device (RCD). This test does not make earthing resistance
measurement (R
E
), or proper checking of the earth conductor condition
redundant, which must be performed separately.
Type -A: Protects against special forms of residual pulsating DC which
have have not been smoothed
Type -G: High reliability against unwanted tripping. Compulsory for any cir-
cuit where personal injury or damage to property may occur in case of
unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6).
Type -G/A: Additionally protects against special forms of residual pulsating
DC which have not been smoothed.
Special types for X-ray application PFIM-...-R
Type -R: To aviod unwanted tripping due to X-ray devices.
Type -S: Selective residual current device sensitive to AC, type -S.
Compulsory for systems with surge arresters downstream of the RCD
(ÖVE/ÖNORM E 8001-1 § 12.1.5).
Type -S/A: Additionally protects against special forms of residual pulsating
pulsating DC which have not been smoothed.
Type -U: Suitable for speed-controlled drives with frequency converters in
household, trade, and industry.
Unwanted tripping is avoided thanks to a tripping characteristic designed
particularly for frequency converters.
See also explanation “Frequency Converter-Proof RCDs - What for?”
Application according to ÖVE/ÖNORM E 8001-1 and Decision EN 219 (1989),
VDE 0100, SEV 1000.
Accessories:
Auxiliary switch for
subsequent installation to the left Z-HK 248432
Tripping signal contact for
subsequent installation to the right Z-NHK 248434
Remote control and
automatic switching device Z-FW/LP 248296
Compact enclosure KLV-TC-2 276240
KLV-TC-4 276241
Sealing cover set Z-RC/AK-2TE 285385
Z-RC/AK-4TE 101062
Switching interlock IS/SPE-1TE 101911
Technical Data
Electrical
Design according to IEC/EN 61008
Type G acc. to ÖVE E 8601
Current test marks as printed onto the device
Tripping instantaneous
Type G, R 10 ms delay
Type S 40 ms delay -
with selective disconnecting
function
Type U (only 30 mA) 10 ms delay
Type U (without 30 mA) 40 ms delay -
with selective disconnecting
function
Rated voltage U
n
230/400 V, 50 Hz
Rated tripping current I
Δn
10, 30, 100, 300, 500 mA
Sensitivity AC and pulsating DC
Rated insulation voltage U
i
440 V
Rated impulse withstand voltage U
imp
4 kV
Rated short circuit strength I
nc
10 kA
Maximum back-up fuse Short circuit
I
n
= 16-63 A 63 A gG/gL
I
n
= 80 A 80 A gG/gL
I
n
= 100 A 100 A gG/gL
Type PFIM-X:
I
n
= 40A 63 A gG/gL
I
n
= 63A 63 A gG/gL
Rated breaking capacity I
m
or
Rated fault breaking capacity I
Δm
I
n
= 16-40 A 500 A
I
n
= 63 A 630 A
I
n
= 80 A 800 A
I
n
= 100 A 1,000 A
Voltage range of test button 2-pole 184 - 250 V~
4-pole 184 - 440 V~
Endurance
electrical comp. 4,000 operating cycles
mechanical comp. 20,000 operating cycles
Mechanical
Frame size 45 mm
Device height 80 mm
Device width 35 mm (2MU),
70 mm (4MU)
Mounting quick fastening with
2 lock-in positions on
DIN rail IEC/EN 60715
Degree of protection, built-in IP40
Deg. of prot. in moisture-proof encl. IP54
Upper and lower terminals open mouthed/lift terminals
Terminal protection finger and hand touch safe,
BGV A3, ÖVE-EN 6
Terminal capacity 1.5 - 35 mm
2
single wire
2 x 16 mm
2
multi wire
Busbar thickness 0.8 - 2 mm
Tripping temperature -25°C to +40°C
Storage- and transport temperature -35°C to +60°C
Resistance to climatic conditions 25-55°C/90-95% relative
humidity acc. to IEC 60068-2
Connection diagrams
2-pole 4-pole
15
26
T
3N
4N