Technical data
44
Protective Devices
Short Circuit Selectivity PFL6-../1N/ towards D01-D03 fuse link
In case of short circuit, there is selectivity between the combined RCD/MCB devices PFL6../1N/ and the upstream fuses up to the specified values of the selec-
tivity limit current I
s
[kA] (i. e. in case of short-circuit currents I
ks
under I
s
, only the MCB will trip, in case of short circuit currents above this value both protec-
tive devices will respond).
*) basically in accordance with EN 60898-1 D.5.2.b
Short circuit selectivity characteristic B towards fuse link D01-D03*)
PFL6
D01-D03 gL/gG
I
n
[A] 10 16 20 25 35 50 63 80 100
6 <0.5
1)
0.5 0.8 2.4 6.0
2)
6.0
2)
6.0
2)
6.0
2)
8 0.6 0.8 2.0 6.0
2)
6.0
2)
6.0
2)
6.0
2)
10 0.5 0.8 1.6 3.7 6.0
2)
6.0
2)
6.0
2)
13 0.6 0.7 1.4 3.0 4.7 6.0
2)
6.0
2)
16 0.6 1.2 2.6 3.9 6.0
2)
6.0
2)
20 1.2 2.5 3.6 6.0
2)
6.0
2)
25 1.2 2.3 3.3 5.7 6.0
2)
1)
Selectivity limit current I
s
under 0.5 kA
2)
Selectivity limit current I
s
= rated breaking capacity I
cn
of the RCD/MCB device
Darker areas: no selectivity
Short circuit selectivity characteristic C towards fuse link D01-D03*)
PFL6
D01-D03 gL/gG
I
n
[A] 10 16 20 25 35 50 63 80 100
6 <0.5
1)
<0.5
1)
0.8 2.3 6.0
2)
6.0
2)
6.0
2)
6.0
2)
8 <0.5 0.7 2.1 5.5 6.0
2)
6.0
2)
6.0
2)
10 <0.5 0.6 1.3 2.9 4.5 6.0
2)
6.0
2)
13 1.2 2.5 3.9 6.0
2)
6.0
2)
16 1.0 2.1 3.0 5.5 6.0
2)
20 1.0 2.0 2.7 5.0 6.0
2)
25 1.9 2.6 4.5 6.0
2)
Short Circuit Selectivity PFL6-../1N/ towards NH-00 fuse link
In case of short circuit, there is selectivity between the combined RCD/MCB devices PFL6../1N/ and the upstream fuses up to the specified values of the selec-
tivity limit current I
s
[kA] (i. e. in case of short-circuit currents I
ks
under I
s
, only the MCB will trip, in case of short circuit currents above this value both protec-
tive devices will respond).
*) basically in accordance with EN 60898-1 D.5.2.b
Short circuit selectivity characteristic B towards fuse link NH-00*)
PFL6
NH-00 gL/gG
I
n
[A] 16 20 25 32 35 40 50 63 80 100 125 160
6 <0.5
1)
0.5 0.8 1.4 2.2 3.3 6.0
2)
6.0
2)
6.0
2)
6.0
2)
6.0
2)
6.0
2)
10 <0.5
1)
0.7 0.9 1.5 2.1 3.4 4.3 6.0
2)
6.0
2)
6.0
2)
6.0
2)
13 <0.5
1)
0.6 0.8 1.4 1.8 2.8 3.6 5.7 6.0
2)
6.0
2)
6.0
2)
16 0.6 0.7 1.2 1.5 2.4 3.0 4.5 6.0
2)
6.0
2)
6.0
2)
20 0.7 1.1 1.5 2.2 2.8 4.2 6.0
2)
6.0
2)
6.0
2)
25 0.7 1.1 1.4 2.1 2.6 4.0 6.0
2)
6.0
2)
6.0
2)
Short circuit selectivity characteristic C towards fuse link NH-00*)
PFL6
NH-00 gL/gG
I
n
[A] 16 20 25 32 35 40 50 63 80 100 125 160
6 <0.5
1)
<0.5
1)
0.7 1.3 2.2 3.3 5.9 6.0
2)
6.0
2)
6.0
2)
6.0
2)
6.0
2)
10 0.5 0.8 1.2 1.7 2.7 3.4 5.5 6.0
2)
6.0
2)
6.0
2)
13 1.1 1.5 2.3 2.9 4.7 6.0
2)
6.0
2)
6.0
2)
16 1.0 1.3 1.8 2.3 3.7 6.0
2)
6.0
2)
6.0
2)
20 0.9 1.1 1.7 2.2 3.4 6.0
2)
6.0
2)
6.0
2)
25 1.6 2.1 3.2 6.0
2)
6.0
2)
6.0
2)










