Technical data
24
Protective Devices
PBR Main Protective Device
ATTENTION:
The main protective device does not replace a residual current device (RCD).
For protection against residual current or additional protection you still need
to install an RCD even if you use a main protective device.
The objective of the PBR main protective device is preventive fire protection
only.
• Tripping current identification (I
Δn
) is independent of the line voltage
• Integrated overload protection
• Contour and busbar compatible with other devices of the P series
• Double-comfort terminal lift/open-mouthed at top and bottom
• Free selection of the busbar arrangement at top and bottom
• Free terminal space despite the fitted busbar
• Universal Z-NHK tripping signal switch can be retro-fitted
• Auxiliary Z-HK switch can be retro-fitted
• Contact position indicator red - green
• Suitable for use with commercially available standard fluorescent lamps
with or without electronic ballast
• The function of the switch is independent of its position
• Mains connection on any side
• The 4-pole switch cannot be used as a 3-pole switch
• The 4-pole switch can also be used as a 2-pole switch
In this case use terminals 1-2 and N-N (+ wire bridge, see instructions).
• The test button “T” needs to be activated once a year. This fact and respon-
sibility needs to be communicated to the system operator in a provable
manner.
• Due to their tripping characteristics the main protective devices feature full
selectivity with regard to downstream electromagnetic quick tripping relays
of MCBs according to EN 60898-1 and of “general” and “S” types of RCD
protective devices according to EN 61008-1.
Main protective devices are particularly important as fire protection in
3L+PEN ~400/230 V networks (TN-systems).
Main protective devices are particularly important as back-up protection
against electrical shocks in 3L+N ~400/230 V networks (TT-systems)
Accessories:
Auxiliary switch
for retro-fitting on the left side (4p) Z-HK 248432
Tripping signal contact
for retro-fitting on the right side Z-NHK 248434
Reset device Z-FW/LP 248296
Small enclosure KLV-TC-4 276241
Lead-seal set Z-RC/AK-4TE 101062
Anti-tamper device IS/SPE-1TE 101911
Technical Data
Electrical
Current test marks as printed onto the device
Tripping 200 ms delayed
selective switch-off
Rated voltage U
n
230/400 V; 50 Hz
Fire protection residual current I
Δn
300 mA
Sensitivity AC
Rated insulation voltage U
i
440 V
Rated peak withstand voltage U
imp
4 kV
Rated short circuit strength I
nc
10 kA
Max. back-up fuse as overload 63 A gG/gL
and short-circuit protection
Rated making and breaking capacity I
m
or
Rated residual making/breaking cap. I
Δm
630 A
Voltage range of test button 195.5 - 440 V~
Endurance electrical ≥ 4.000 operating cycles
mechanical ≥ 20.000 operating cycles
Mechanical
Frame size 45 mm
Device height 80 mm
Installation width 70 mm (4U)
Mounting Quick fastening with
2 lock-in positions for
DIN rail IEC/EN 60715
Degree of protection, built-in IP40
Upper and lower terminals Open-mouthed/lift terminals
Terminal protection Finger and hand touch safe
acc. to BGV A3, ÖVE-EN 6
Terminal capacity 1.5 - 35 mm
2
single-wired
2 x 16 mm
2
multi-wired
Material thickness of busbar 0.8 - 2 mm
Permitted ambient temperature range -25°C to +40°C
Resistance to climatic conditions 25-55°C/90-95% relative
humidity acc. to IEC 60068-2
Dimensions (mm)
Connection diagram
4-pole