Technical data

20
Protective Devices
Add-on Residual Current Protection Unit PBSM
Add-on residual current unit
Line voltage-independent tripping
By combining this device with a top-quality miniature circuit breaker type PLS.
(exept PLSN.) a top-quality RCBO unit (combined RCD/MCB device) is formed.
Rated current 40 and 63 A
Permits combinations with a variety of characteristics thanks to the differ-
ent rated currents and characteristics of the PLS.-miniature cirvuit breakers
which can be connected
Comrehensive range of accessories suitable for subsequent installation
onto PLS.
Type -A: Protect against special forms of residual pulsating DC which have
not been smoothed.
Type -G: High reliability against unwanted tripping. Compulsory for any cir-
cuit where personal injury or damage to property may occur in case of
unwanted tripping (ÖVE-EN1, Part1, §12.14).
Type -S: Selective residual current device, either sensitive to AC, type -S,
or sensitive to pulsating DC, type -S/A, for protection against special forms
of residual pulsating DC which have not been smoothed. Compulsory for
systems with surge arresters downstream of the RCD (ÖVE-EN1, Part 1,
§12.15).
Accessories :
Cover cap for draw-out connection bar included
Slotted one-way cheese head screw included
Accessories (on PLS.):
Auxiliary switch for
subsequent installation ZP-IHK 286052
ZP-WHK 286053
Tripping signal contact for
subsequent installation ZP-NHK 248437
Remote control and automatic switching device
Z-FW/LP 248296
Shunt trip release ZP-ASA/.. 248438, 248439
Undervoltage release Z-USA/.. 248288-248291
Compact enclosure KLV-TC-2 276240
KLV-TC-4 276241
Additional terminal 35mm
2
Z-HA-EK/35 263960
Switching interlock IS/SPE-1TE 101911
Technical Data
Electrical
Design according to IEC/EN 61009
Current test marks as printed onto the device
Tripping
instantaneous 250A (8/20µs),
surge current-proof
Type G 10 ms delay 3kA (8/20µs),
surge current-proof
Type S 40 ms delay 6kA -
with selective disconnecting
function
Rated voltage U
n
230/400 V AC
Operational voltage range 196 - 440 V
Rated frequency 50 Hz
Use at 16
2
/3 Hz Recesses time between the
single switchings increases
to 88 s, I
n
max. 63 A
Use at 400 Hz I
n
max. 40 A
Rated current I
n
40 A, 63 A
Rated tripping current I
Δn
30, 100, 300, 500, 1000 mA
Rated non-tripping current I
Δno
0.5 I
Δn
Sensitivity AC and pulsating DC
Service short circuit breaking capacity I
cs
same as connected PLS. (7.5 kA)
Rated breaking capacity I
cn
same as connected PLS. (10 kA)
Rated fault breaking capacity I
Δm
6 kA (U
n
= 230V)
3 kA (U
n
= 400V)
Mechanical
Frame-size 45 mm
Device height 90 mm
Device width 70 mm (2p), 107.5 mm (3p),
125 mm (4p)
Mounting fix mounted onto PLS.
Degree of protection installed device IP40
Fastening screw M 2.5 (slotted one-way
cheese head screw;
Screw head breaking torque > 0.6 Nm
Upper and lower terminals lift terminals
Terminal screws M 5 (combined Philips/stan-
dard head screws according
to DIN7962-Z2, Pozidrive)
Terminal protection finger and hand touch safe,
BGV A3, ÖVE-EN 6
Terminal capacity
Rigid conductors 1 x (1 - 25) mm
2
Flexible conductors (with wire
end sleeve) 1 x (0.75 - 16) mm
2
Busbar thickness 0.8 - 2 mm
Permitted ambient temperature range -25°C to +40°C
Resistance to climatic conditions acc. to IEC/EN 60068-2
(25..55°C/90..95% relative humidity)
Dimensions (mm)
Connection diagramms
2-pole 3-pole 4-pole
2’
2
T
4’
4
2’
2
6’
6
T
4’
4
2’
2
6’
6
T
4’
4
8N’
8N