Technical data

15
Protective Devices
Dimensions (mm)
Correct connection
3+N
(230/400V)
Local Indication RCCB
Status indication LED red / yellow / green
Permanent light green Normal operation
Permanent light yellow The measured residual current is bigger than 30% of the nominal
tripping value.
Permanent light red The measured residual current is bigger than 50% of the nominal
tripping value.
Remote Indication
Standard Version: 1 contact NO up to 230V AC, 2 terminals, 1 A ohmic load
Optional Version: (available upon request) 1 NO + 1 NC up to 110V AC/contact, 2x2 terminals, 1 A ohmic load
Terminal capacity of contacts: 0.25 - 1.5 mm
2
3phase load without N
(184V-254V AC Phase-Phase)
1+N (230V)
3phase load without N
(400V AC Phase-Phase)
Test button works within 184V – 440V AC !, Electronic works within 50-254V AC !