Technical data
14
Protective Devices
Residual Current Devices dRCM - digital
• Residual current devices
• Shape compatible with and suitable for standard busbar connection to
other devices of the P-series
• Twin-purpose terminal (lift/open-mouthed) above and below
• Busbar positioning optionally above or below
• Free terminal space despite installed busbar
• Universal tripping signal switch, also suitable for PLS., PKN., ZP-A. can be
mounted subsequently
• Auxiliary switch Z-HK can be mounted subsequently
• Contact position indicator red - green
• Tripping indicator white - blue
• Additional Safety
- possibility to seal
- possibility to lock in ON and OFF position
• Delayed types suitable for being used with standard fluorescent tubes with
or without electronical ballast (30mA-RCD: 30 units per phase conductor,
100mA-RCD: 90 units per phase conductor)
Notes: Depending of the fluorescent lamp ballast manufacturer partly more
possible. Symmetrical allocation of the fluorescent lamp ballasts on all
phases favourably. Shifting references of the fluorescent lamp ballast man-
ufacturer consider.
• The device functions irrespective of the position of installation
• Tripping is line voltage-independent. Consequently, the RCD is suitable for
“fault current/residual current protection” and “additional protection” with-
in the meaning of the applicable installation rules
• Mains connection at either side
• The 4-pole device can also be used for 3-pole connection:
See connection possibilities.
• The 4-pole device can also be used for 2-pole connection:
See connection possibilities.
• The test key “T” must be pressed every year. The system operator must be
informed of this obligation and his responsibility in a way that can be
proven. The yearly test interval is only valid for residential and similar
applications. Under all other conditions (e.g. damply or dusty environ-
ment), it's recommended to test in shorter intervals (e.g. monthly).
A test is further needed if red and yellow LED are on together.
• Pressing the test key “T” serves the only purpose of function testing the
residual current device (RCD). This test does not make earthing resistance
measurement (R
E
), or proper checking of the earth conductor condition
redundant, which must be performed separately.
• Functioning
- The green LED becomes active at 0-30% I
Δn
- The yellow LED becomes active at 30-50% I
Δn
- The red LED becomes active at >50% I
Δn
• Potential-free relay (NO contact, in parallel with the yellow LED, up to 1 A
ohmic load / 230 V~) for external prewarning function. Bistabile, means the
warning stays on also when the breaker trips, until reset.
• Type -A: Protects against special forms of residual pulsating DC which
have have not been smoothed
• Type -G: High reliability against unwanted tripping. Compulsory for any cir-
cuit where personal injury or damage to property may occur in case of
unwanted tripping (ÖVE/ÖNORM E 8001-1 § 12.1.6).
• Type -G/A: Additionally protects against special forms of residual pulsating
DC which have not been smoothed.
• Type -R: To aviod unwanted tripping due to X-ray devices.
• Type -S: Selective residual current device sensitive to AC, type -S.
Compulsory for systems with surge arresters downstream of the RCD
(ÖVE/ÖNORM E 8001-1 § 12.1.5).
• Type -S/A: Additionally protects against special forms of residual pulsating
pulsating DC which have not been smoothed.
• Type -U: Suitable for speed-controlled drives with frequency converters in
household, trade, and industry.
Unwanted tripping is avoided thanks to a tripping characteristic designed
particularly for frequency converters.
See also explanation “Frequency Converter-Proof RCDs - What for?”
Application according to ÖVE/ÖNORM E 8001-1 and Decision EN 219 (1989),
VDE 0100, SEV 1000.
Accessories:
Auxiliary switch for
subsequent installation to the left Z-HK 248432
Tripping signal contact for
subsequent installation to the right Z-NHK 248434
Remote control and
automatic switching device Z-FW/LP 248296
Compact enclosure KLV-TC-4 276241
Sealing cover set Z-RC/AK-4TE 101062
Switching interlock IS/SPE-1TE 101911
Technical Data
Electrical
Design according to IEC/EN 61008
Type G and G/A acc. to
ÖVE E 8601
Current test marks as printed onto the device
Tripping instantaneous
Type G , R 10 ms delay
Type S 40 ms delay -
with selective disconnecting
function
Type U (only 30 mA) 10 ms delay
Type U (without 30 mA) 40 ms delay -
with selective disconnecting
function
Rated voltage U
n
230/400 and 240/415 V AC,
50/60 Hz
Operation voltage electronic 50 – 254V AC
Operation voltage test circuit 184 – 440V AC
Rated tripping current I
Δn
30, 300 mA
Sensitivity AC and pulsating DC
Rated insulation voltage U
i
440 V
Rated impulse withstand voltage U
imp
4 kV (1.2/50 µs)
Rated short circuit capacity I
nc
10 kA
Peak withstand current
Type G, G/A, R, U (30mA) 3 kA (8/20 µs)
surge current proof
Type S/A, U (except 30mA) typ. 5 kA (8/20 µs)
selective + surge current
proof
Electrical isolation > 4 mm contact space
Maximum back-up fuse Short circuit and
overload protection
I
n
= 16-63A 63 A gG/gL
I
n
= 80A 80 A gG/gL
I
n
= 100A 100 A gG/gL
Endurance
electrical comp. ≥ 4,000 operating cycles
mechanical comp. ≥ 20,000 operating cycles
Mechanical
Frame size 45 mm
Device height 80 mm
Device width 70 mm (4MU)
Mounting quick fastening with
2 lock-in positions on
DIN rail IEC/EN 60715
Degree of protection, built-in IP40
Deg. of prot. in moisture-proof encl. IP54
Upper and lower terminals open mouthed/lift terminals
Terminal protection finger and hand touch safe,
BGV A3, ÖVE-EN 6
Terminal capacity 1.5 - 35 mm
2
single wire
2 x 16 mm
2
multi wire
Terminal screw M5 (Pozidriv PZ2)
Terminal capacity warning contact(s)
0.25-1.5 mm
2
(plug in terminals)
Terminal torque 2 - 2.4 Nm
Busbar thickness 0.8 - 2 mm
Tripping temperature -25°C to +40°C
Storage- and transport temperature -35°C to +60°C
Resistance to climatic conditions 25-55°C/90-95% relative
humidity acc. to IEC 60068-2
Contact position indicator red / green
Tripping indicator white / blue
Connection diagram
4-pole