Technical data

128
Power Limiter Z-TS
Design according to EN/IEC 60898-1
Shape compatible with and suitable for standard busbar connection to e.g.
CLS6, Z-A40, Z-MS, PFIM
Switching device for voluntary or power-authority limitation of power con-
sumption of user systems and equipment
Approved by the Austrian regional power supply companies, easy to re-set
by the customer
1- and 3-pole design
Adjustment screw for setting range under sealable cover cap
Technical Data
Electrical
Rated voltage 230/400 VAC
Frequency 50 Hz
Rated breaking capacity
20-32 A 10 kA
40-63 A 6 kA
Max. back-up fuse, short-circuit 100 A gG
Rated current
Z-TS20/. 20 A
Z-TS25/. 25 A
Z-TS32/. 32 A
Z-TS40/. 40 A
Z-TS50/. 50 A
Z-TS63/. 63 A
Setting range
Z-TS20/. 13-20 A
Z-TS25/. 16-25 A
Z-TS32/. 20-32 A
Z-TS40/. 25-40 A
Z-TS50/. 40-50 A
Z-TS63/. 50-63 A
Mechanical
Frame size 45 mm
Device height 80 mm
Device width 17.5 mm (1P); 52.5 mm (3P)
Mounting quick fastening on
DIN rail IEC/EN 60715
Degree of protection, built-in IP40
Upper and lower terminals cage-type terminals
Terminal capacity 1.5-25 mm
2
Dimensions (mm)
Accessories
Busbar block ZV7
Auxiliary switch and tripping signal switch Z-AHK, Z-NHK
Shunt trip release and undervoltage release Z-ASA, Z-USA
Moisture-proof enclosure Z-MFG
Connection diagram
1-pole 3-pole
Protective Devices