Technical data

12
Protective Devices
Residual Current Devices PFDM
Residual current devices
Tripping is line voltage-independent. Consequently, the RCD is suitable for
the protection of humans and additional protection (ÖVE/ÖNORM E 8001-1
§ 6.1.2)
Twin-purpose terminal (lift/open-mouthed) above and below
Not busbar-compatible with other devices of the P-series
Auxiliary switch Z-HD can be mounted subsequently
Contact position indicator red - green
The device functions irrespective of the position of installation
Tripping is line voltage-independent. Consequently, the RCD is suitable for
“fault current/residual current protection” and “additional protection” with-
in the the meaning of the applicable installation rules
Mains connection at either side
The test key “T” must be pressed every month. The system operator must
be informed of this obligation and his responsibility in a way that can be
proven (self-adhesive RCD-label enclosed)
Type -A: Additionally protects against special forms of residual pulsating
DC which have not been smoothed.
Type -S/A: Compulsory for systems with surge arresters downstream of
the RCD (ÖVE/ÖNORM E 8001-1 § 12.1.5).
Accessories:
Auxiliary switch for
subsequent installation to the left Z-HD 265620
Technical Data PFDM
Electrical
Design according to IEC/EN 61008
Current test marks as printed onto the device
Tripping instantaneous
Typ S/A 40 ms delay -
with selective disconnecting
function
Rated voltage U
n
230/400 V; 50 Hz
Rated tripping current I
Δn
30, 100, 300, 500 mA
Sensitivity AC and pulsating DC
Rated short circuit strength I
nc
10 kA with back-up fuse
Maximum back-up fuse Short circuit 125 A gG/gL
Rated breaking capacity I
m
or
Rated fault breaking capacity I
Δm
1250 A
Voltage range of test button
2-pole 100 - 250 V~
4-pole 185 - 440 V~
Endurance electrical comp. 4,000 operating cycles
mechanical comp. 20,000 operating cycles
Mechanical
Frame size 45 mm
Device height 85 mm
Device width 36 mm (2P), 72 mm (4P)
Mounting quick fastening on
DIN rail IEC/EN 60715
Degree of protection, built-in IP40
Upper and lower terminals open mouthed/lift terminals
Terminal protection finger and hand touch safe,
BGV A3, ÖVE-EN 6
Terminal capacity 1.5 - 50 mm
2
Busbar thickness 0.8 - 2 mm
Tripping temperature -25°C to +40°C
Storage- and transport temperature -35°C to +60°C
Resistance to climatic conditions 25-55°C/90-95% relative
humidity acc. to IEC 60068-2
Dimensions (mm)
Connection diagrams
2-pole 4-pole Z-HD
Function Auxiliary Switch
Tripping signal switch: detects if RCD tripping occured by
an fault current
Auxiliary switch: shows the contact position of the RCD
Technical Data Auxiliary Switch Z-HD
Electrical
Subsequent installation to the left onto
PFDM
Contacts 1CO + 1NC
Load rating
AC11 6 A / 230 V AC
DC11 1 A / 230 V DC
Mechanical
Terminal capacity up to 2.5 mm
2