Technical data
12
Protective Devices
Residual Current Devices PFDM
• Residual current devices
• Tripping is line voltage-independent. Consequently, the RCD is suitable for
the protection of humans and additional protection (ÖVE/ÖNORM E 8001-1
§ 6.1.2)
• Twin-purpose terminal (lift/open-mouthed) above and below
• Not busbar-compatible with other devices of the P-series
• Auxiliary switch Z-HD can be mounted subsequently
• Contact position indicator red - green
• The device functions irrespective of the position of installation
• Tripping is line voltage-independent. Consequently, the RCD is suitable for
“fault current/residual current protection” and “additional protection” with-
in the the meaning of the applicable installation rules
• Mains connection at either side
• The test key “T” must be pressed every month. The system operator must
be informed of this obligation and his responsibility in a way that can be
proven (self-adhesive RCD-label enclosed)
• Type -A: Additionally protects against special forms of residual pulsating
DC which have not been smoothed.
• Type -S/A: Compulsory for systems with surge arresters downstream of
the RCD (ÖVE/ÖNORM E 8001-1 § 12.1.5).
Accessories:
Auxiliary switch for
subsequent installation to the left Z-HD 265620
Technical Data PFDM
Electrical
Design according to IEC/EN 61008
Current test marks as printed onto the device
Tripping instantaneous
Typ S/A 40 ms delay -
with selective disconnecting
function
Rated voltage U
n
230/400 V; 50 Hz
Rated tripping current I
Δn
30, 100, 300, 500 mA
Sensitivity AC and pulsating DC
Rated short circuit strength I
nc
10 kA with back-up fuse
Maximum back-up fuse Short circuit 125 A gG/gL
Rated breaking capacity I
m
or
Rated fault breaking capacity I
Δm
1250 A
Voltage range of test button
2-pole 100 - 250 V~
4-pole 185 - 440 V~
Endurance electrical comp. ≥ 4,000 operating cycles
mechanical comp. ≥ 20,000 operating cycles
Mechanical
Frame size 45 mm
Device height 85 mm
Device width 36 mm (2P), 72 mm (4P)
Mounting quick fastening on
DIN rail IEC/EN 60715
Degree of protection, built-in IP40
Upper and lower terminals open mouthed/lift terminals
Terminal protection finger and hand touch safe,
BGV A3, ÖVE-EN 6
Terminal capacity 1.5 - 50 mm
2
Busbar thickness 0.8 - 2 mm
Tripping temperature -25°C to +40°C
Storage- and transport temperature -35°C to +60°C
Resistance to climatic conditions 25-55°C/90-95% relative
humidity acc. to IEC 60068-2
Dimensions (mm)
Connection diagrams
2-pole 4-pole Z-HD
Function Auxiliary Switch
Tripping signal switch: detects if RCD tripping occured by
an fault current
Auxiliary switch: shows the contact position of the RCD
Technical Data Auxiliary Switch Z-HD
Electrical
Subsequent installation to the left onto
PFDM
Contacts 1CO + 1NC
Load rating
AC11 6 A / 230 V AC
DC11 1 A / 230 V DC
Mechanical
Terminal capacity up to 2.5 mm
2