Technical data

104
Miniature Circuit Breakers CLS.
High selectivity between MCB and back-up fuse due to low let-through
energy
Twin-purpose terminal (lift/open-mouthed) above and below
Compatible with standard busbar
Meets the requirements of insulation co-ordination,
distance between contacts 4 mm, for secure isolation
Suitable for applications up to 48 V DC (use CLS6-DC for higher DC volt-
ages)
Accessories:
Auxiliary switch for
subsequent installation Z-AHK 248433
Tripping signal contact for
subsequent installation Z-NHK 248434
Remote control and automatic switching device
Z-FW/LP 248296
Shunt trip release ZP-ASA 248438, 248439
Undervoltage release Z-USA/.. 248288-248291
Compact enclosure KLV-TC-2 276240
KLV-TC-4 276241
Additional terminal 35mm
2
Z-HA-EK/35 263960
Switching interlock Z-IS/SPE-1TE 274418
Technical Data
Electrical
Design according to IEC/EN 60898-1
Current test marks as printed onto the device
Rated voltage AC: 230/400V
DC: 48V (per pole,
max. 2 Pole)
Rated frequency 50/60 Hz
Rated breaking capacity according to IEC/EN 60898-1
CLS6 6 kA
CLS4 4.5 kA
Characteristic B, C, D
Back-up fuse
>6 kA max. 100 A gL
>4.5 kA max. 80 A gL
Selectivity class 3
Endurance 8,000 operating cycles
Line voltage connection optional (above/below)
Mechanical
Frame size 45 mm
Device height 80 mm
Device width 17.5 mm per pole (1MU)
26.3 mm: device 1P+N (1.5MU)
Mounting quick fastening with
2 lock-in positions on
DIN rail IEC/EN 60715
Degree of protection IP20
Upper and lower terminals open mouthed/lift terminals
Terminal protection finger and hand touch safe,
BGV A3, ÖVE-EN 6
Terminal capacity 1-25 mm
2
Terminal fastening torque 2-2.4 Nm
Busbar thickness 0.8 - 2 mm
Dimensions (mm)
Connection diagrams
1-pole 1+N-pole 2-pole
3-pole 3+N-pole 4-pole