Technical data

10
Protective Devices
Residual Current Relays PFR., Core Balance Transformers Z-WFR.
Residual current relays
Shape compatible with and suitable for standard busbar connection to
other devices of the P-series
Universal tripping signal switch, also suitable for PLS., PKN., Z-A. can be
mounted subsequently
Auxiliary switch Z-HK can be mounted subsequently
Contact position indicator red - green
Delayed types suitable for being used with standard fluorescent tubes with
or without electronical ballast (30mA-RCD: 30 units per phase conductor,
100mA-RCD: 90 units per phase conductor)
Notes: Depending of the fluorescent lamp ballast manufacturer partly more
possible. Symmetrical allocation of the fluorescent lamp ballasts on all
phases favourably. Shifting references of the fluorescent lamp ballast man-
ufacturer consider.
The test key “T” must be pressed every month. The system operator must
be informed of this obligation and his responsibility in a way that can be
proven (self-adhesive RCD-label enclosed)
Type -U: Suitable for speed-controlled drives with frequency converters in
household, trade, and industry.
Unwanted tripping is avoided thanks to a tripping characteristic designed
particularly for frequency converters.
See also explanation “Frequency Converter-Proof RCDs - What for?”
Application according to ÖVE/ÖNORM E 8001 and Decision EN 219 (1989),
VDE 0100, SEV 1000.
Accessories:
Auxiliary switch for
subsequent installation to the left Z-HK 248432
Tripping signal contact for
subsequent installation to the right Z-NHK 248434
Compact enclosure KLV-TC-4 276241
Sealing cover set Z-RC/AK-4TE 101062
Switching interlock IS/SPE-1TE 101911
Technical Data
Electrical
Design according to IEC/EN 61008
Current test marks as printed onto the device
Tripping 40 ms delay
with selective disconnecting
function
Rated voltage U
n
230/400 V; 50 Hz
Rated tripping current I
Δn
(0.1)
*)
, 0.3 and 1 A
Rated current 25 A / 400 V~,
of relay contacts 16 A / 230 V AC 15
Maximum nominal current 400 A
Sensitivity pulsating DC
Rated peak withstand voltage U
imp
4 kV (1.2/50µs)
Voltage range of test button 184 - 440 V~
Endurance electrical comp. 4,000 operating cycles
mechanical comp. 20,000 operating cycles
Mechanical
Frame size 45 mm
Device height 80 mm
Device width 70 mm (4MU)
Mounting quick fastening with
2 lock-in positions on
DIN rail IEC/EN 60715
Degree of protection, built-in IP40
Upper and lower terminals open mouthed/lift terminals
Terminal protection finger and hand touch safe,
BGV A3, ÖVE-EN 6
Terminal capacity 1.5 - 35 mm
2
single wire
2 x 16 mm
2
multi wire
Busbar thickness 0.8 - 2 mm
Control line 1.5 - 2.5 mm
2
Tripping temperature -25°C to +40°C
Storage- and transport temperature -35°C to +60°C
Resistance to climatic conditions 25-55°C/90-95% relative
humidity acc. to IEC 60068-2
*)
see Important Information for Installation
Dimensions (mm)
45
10,5
4,530,5
44
60
5,5
70
80
4P
Connection diagrams
Relay Core balance transformer
1324
1
2
3
4
L1 L3L2 N
PFR
Z-WFR 2-S/A / Z-WFR 2-U
Z-WFR 3-S/A / Z-WFR 3-U