Specification

Upgraded Generator Transfer Device
for generator or central inverter
supplied lighting
Specifications Key Upgraded Features:
Dual listed to UL 1008 (transfer switch) and UL 924 (switch bypass)
0-10V dimming control override capable
Reduced AC line current and power consumption
Universal input 120-277 VAC, 50/60 Hz
24VDC fire alarm override capable
Dimensions
6.61" x 2.32" x 1.50" (mounting center - 5.98”)
UL Listed
UL 924 and UL 1008 Listed for use as a
Switch Bypass or Branch Circuit Emergency
Lighting Transfer Switch (BCELTS) factory
orfield installation
Full Warranty
5 Years (NOT pro-rata)
Universal Input Voltage
120 through 277 VAC, 50/60 Hz
AC Input Current
30 mA
AC Input Power Rating
2.3 Watts
Switched Load Rating
Up to 277VAC at a maximum load
current of 2 amps
Temperature Rating (Ambient)
-20°C to +65°C (-4°F to 149°F)
Dimensions
6.61" x 2.32" x 1.50" (168 x 59 x 38 mm)
Mounting Center 5.98" (152 mm)
Weight
1.00 lbs. (0.45 kg)
GTDU.spec.L8191112 www.bodine.com 11/19 page 1 of 2
Project:
Location:
Cat.No:
Type:
Lamps: Qty:
Notes:
Auxiliary Power
Control Device
GTDU
6.61 in
168 mm
5.43 in
138 mm
1.5 in
38 mm
2.32 in
59 mm
Benefits:
Allows ON/OFF switching of generator or central inverter
supplied emergency lighting
Can be used with incandescent, fluorescent or LED lighting
loads and provide full light output when in normal mode
Suitable for indoor or damp locations and plenum rated
luminaires/enclosures
2A electronic ballast/driver rating
No batteries required
Meets or exceeds Life Safety Code requirements
Full 5-year (NOT pro-rata) warranty from date of purchase
Product order number: 12 NC number:
GTDUM 913702479201