Cut Sheet
Revised 04/17/13
Data is based upon tests performed by Advance Transformer in a controlled environment and representative of relative performance. Actual performance can vary depending
on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted.
ADVANCE TRANSFORMER CO.
O'HARE INTERNATIONAL CENTER · 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Customer Support/Technical Service: Phone: 800-372-3331 · Fax: 847-768-7768
Corporate Offices: Phone: 800-322-2086
ICN-2S110-SC@120V
Brand Name
CENTIUM
Ballast Type
Electronic
Starting Method
Rapid Start
Lamp Connection
Series
Input Voltage
120-277
Input Frequency
50/60 HZ
Status
Active
Electrical Specifications
Lamp Type Num.
of
Lamps
Rated
Lamp Watts
Min. Start
Temp (°F/C)
Input Current
(Amps)
Input Power
(ANSI
Watts)
Ballast
Factor
MAX
THD
%
Power
Factor
MAX Lamp
Current Crest
Factor
B.E.F.
F48T12/HO 1 60 -20/-29 0.43 49 1.15 10 0.95 1.7 2.35
F48T12/HO 2 60 -20/-29 0.82 93 0.90 10 0.95 1.7 0.97
F60T12/HO 1 75 -20/-29 0.52 59 1.10 10 0.95 1.7 1.86
F60T12/HO 2 75 -20/-29 0.98 116 1.00 10 0.98 1.7 0.86
F72T12/HO 1 85 -20/-29 0.63 72 1.10 10 0.95 1.7 1.53
F72T12/HO 2 85 -20/-29 1.19 140 0.90 10 0.98 1.7 0.64
F96T12/HO 1 110 -20/-29 0.88 100 0.91 10 0.95 1.6 0.91
* F96T12/HO 2 110 -20/-29 1.57 189 0.89 10 1.00 1.6 0.47
F96T12/HO/ES 1 95 60/16 0.68 78 0.91 10 0.95 1.6 1.17
F96T12/HO/ES 2 95 60/16 1.27 152 0.85 10 1.00 1.6 0.56
Wiring Diagram
The wiring diagram that appears above is for
the lamp type denoted by the asterisk (*)
Standard Lead Length (inches)
in. cm.
Black 25 63.5
White 25 63.5
Blue 46 116.8
Red 46 116.8
Yellow 79 200.7
Gray 0
Violet 0
in. cm.
Yellow/Blue 0
Blue/White 0
Brown 0
Orange 0
Orange/Black 0
Black/White 0
Red/White 0
Enclosure
Enclosure Dimensions
OverAll (L) Width (W) Height (H) Mounting (M)
9.50 " 1.7 " 1.18 " 8.90 "
9 1/2 1 7/10 1 9/50 8 9/10
24.1 cm 4.3 cm 3 cm 22.6 cm