Cut Sheet

Revised 08/15/2006
Data is based upon tests performed by Advance Transformer in a controlled environment and representative of relative performance. Actual performance
can vary depending on operating conditions. Specifications are subject to change without notice. All specifications are nominal unless otherwise noted.
ADVANCE
O'HARE INTERNATIONAL CENTER · 10275 WEST HIGGINS ROAD · ROSEMONT, IL 60018
Customer Support/Technical Service: Phone: 800-372-3331 · Fax: 630-307-3071
Corporate Offices: Phone: 800-322-2086
ICF-2S13-H1-LD@120
Brand Name SMARTMATE
Ballast Type Electronic
Starting Method Programmed Start
Lamp Connection Series
Input Voltage 120-277
Input Frequency 50/60 HZ
Status Active
Electrical Specifications
Lamp Type Num.
of
Lamp
s
Rated
Lamp
Watts
Min. Start
Temp
(°F/C)
Input
Current
(Amps)
Input
Power
(ANSI
Watts)
Ballast
Factor
MAX
THD
%
Power
Factor
MAX Lamp
Current
Crest Factor
B.E.F.
* CFQ13W/G24Q 1 13 0/-18 0.13 16 1.00 10 0.96 1.5 6.25
CFQ13W/G24q 2 13 0/-18 0.25 29 1.00 10 0.99 1.5 3.45
CFS10W/GR10Q 1 10 0/-18 0.11 13 1.05 15 0.96 1.5 8.08
CFS10W/GR10Q 2 10 0/-18 0.19 23 0.95 15 0.97 1.5 4.13
CFS16W/GR10q 1 16 0/-18 0.14 17 1.00 12 0.96 1.5 5.88
CFTR13W/GX24Q 1 13 0/-18 0.13 16 1.00 10 0.96 1.5 6.25
CFTR13W/GX24Q 2 13 0/-18 0.25 29 1.00 10 0.99 1.5 3.45
Wiring Diagram
WIRING: (2) LAMPS (1) LAMP
Green Terminal must be Grounded
GREEN
BLACK
WHITE
BALLAST
LINE
BLUE
RED
YELLOW
RED
BLUE
The wiring diagram that appears above is
for the lamp type denoted by the asterisk (*)
Standard Lead Length (inches)
in. cm.
Black 0.0
White 0.0
Blue 0.0
Red 0.0
Yellow 0
Gray
Violet
in. cm.
Yellow/Blue
Blue/White
Brown
Orange
Orange/Black
Black/White
Red/White
Enclosure
Enclosure Dimensions
OverAll (L) Width (W) Height (H) Mounting (M)
4.98 " 2.4 " 1.0 " 4.6 "
4 49/50 2 2/5 1 4 3/5
12.6 cm 6.1 cm 2.5 cm 11.7 cm

Summary of content (2 pages)