Datasheet
Combined visual-audible signaling devices
169
Further technical information can be found on our website at www.pfannenberg.com
Visual-audible
signaling devices
www.pfannenberg.com
168
Flashing Sounders PATROL series 100/105 dB(A) / 5/10 J
PA X 1-05 / PA X 5-05 / PA X 5-10
PATROL - the new generation of sounder/ashing light combinations.
Three dimensional innovation;
• safe; an incorrect installation is virtually impossible
• easy; signicantly shorter assembly and installation times
• economical; extremely high efciency and good penetration of acoustical
obstacles signicantly reduce the required number of sounders
• pre-wired sounder and light ex works
• corresponding light intensity available for every sound pressure level
IP 66
Protection
system
+ 55 °C
- 40 °C
Operating
temperature
Electrical data PA X 1-05
Rated voltage 230 V AC 115 V AC 24 V AC 48 V DC 24 V DC 12 V DC
Rated frequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz
Operating range 187 – 255 V 90 – 135 V 18 – 30 V 40 – 60 V 18 – 30 V 12 – 15 V
Nominal current consumption
1
65 – 70 mA 110 – 130 mA 860 – 920 mA 190 – 150 mA 315 – 365 mA 610 – 625 mA
Mechanical data PA X 1-05 PA X 5-05 PA X 5-10
Sound pressure level 100 dB (A) 105 dB (A) 105 dB (A)
Sound level reduction max. - 16 dB via potentiometer
Alarm tones 80 (see tone table page 172/173)
Flash energy 5 J 5 J 10 J
Flash rate 1 Hz = 60 ashes/min.
Light intensity (DIN 5037)
1
44 cd 47 cd 92 cd
Operating temperature - 40 °C ... + 55 °C
Storage temperature - 40 °C ... + 70 °C
Relative humidity 90%
Protection system according to EN 60529 IP 66
Protection class II
Duty cycle 100%
Service life of the ash tube light emission still 70% after 8 000 000 ashes
Material
sounder PC / ABS blend
lens ashing light polycarbonate (PC)
Colour
housing similar to RAL 3000 (ame red) / RAL 7035 (light grey) / RAL 9003 (signal white)
lens ashing light clear, white, yellow, amber, red, green, blue
Cable entry 3 x M20 knock-outs on side, 1 knock-out on back
Integrated seal with cable entry 6 – 13 mm (feed-through grommet)
Connecting terminals 2.5 mm
2
ne wire with cable end sleeve, AWG 16
Weight
AC 725 g 983 g
DC 560 g 800 g
1
with a clear lens
r =
18 m
Acoustic
range
r =
32 m
Acoustic
range
PA X 1 PA X 5
EN
54-3
24 V DC,
48 V DC
EN
54-23
24 V DC,
48 V DC
VdS
24 V DC,
48 V DC
PA X 1 PA X 1 PA X 1
Options / Accessories
Conformity to standards
The acoustic parameters conform to the European standard DIN EN ISO 7731;
“Ergonomic – alarm signals for public areas and workplaces – acoustic alarm signals“.
The requirement for an acoustic alarm signal can be found in the harmonised standards:
EN 60204-1 Electrical equipment of machines
EN 60825-1 Radiation safety of laser devices, identical to IEC 825 and DIN-VDE 0837
Dimensions
PA X 1-05 PA X 5-05
Ordering details
Article numbers
PA X 5-05 – housing red PA X 5-05 – housing grey
Version Rated voltage 230 V AC 115 V AC 24 V DC 230 V AC 115 V AC 24 V DC
yellow lens 233 51 10 3 000 233 51 15 3 000 233 51 80 3 000 233 51 10 3 055 233 51 15 3 055 233 51 80 3 055
amber lens 233 51 10 4 000 233 51 15 4 000 233 51 80 4 000 233 51 10 4 055 233 51 15 4 055 233 51 80 4 055
red lens 233 51 10 5 000 233 51 15 5 000 233 51 80 5 000 233 51 10 5 055 233 51 15 5 055 233 51 80 5 055
Article numbers for other voltages and versions on request
109.5
86.4
98
Ø 6.3
172.4
37
22
80.6
132
135
M20 knock-outs
prepared
215
163.4
143
Ø 7.3
GL
Enclo-
sure
tting
See page 173 for further information
Surface
gasket
Tamper-
proof
sealing
Article numbers
PA X 1-05 – housing red PA X 1-05 – housing grey
Version Rated voltage 230 V AC 115 V AC 24 V DC 230 V AC 115 V AC 24 V DC
yellow lens 233 11 10 3 000 233 11 15 3 000 233 11 80 3 000 233 11 10 3 055 233 11 15 3 055 233 11 80 3 055
amber lens 233 11 10 4 000 233 11 15 4 000 233 11 80 4 000 233 11 10 4 055 233 11 15 4 055 233 11 80 4 055
red lens 233 11 10 5 000 233 11 15 5 000 233 11 80 5 000 233 11 10 5 055 233 11 15 5 055 233 11 80 5 055
Electrical data PA X 5
Rated voltage 230 V AC 115 V AC 24 V AC 48 V DC 24 V DC 12 V DC
Rated frequency 50 / 60 Hz 50 / 60 Hz 50 / 60 Hz
Operating range 187 – 255 V 90 – 135 V 18 – 30 V 40 – 60 V 18 – 30 V 12 – 15 V
Nominal current consumption
1
5 J 65 – 70 mA 110 – 130 mA 860 – 920 mA 190 – 150 mA 315 – 365 mA 610 – 625 mA
10 J 150 – 155 mA 250 – 260 mA 1 460 – 1 520 mA 320 – 380 mA 565 – 620 mA 1 200 – 1 220 mA
1
power consumption dependent on operating voltage
UL
Acoustic
penetration