Instructions
VersiDrive i E3 User Guide Revision 1.03
www.peter-electronic.com
23
7 Analog and Digital Input Macro Configurations
P-15 DI1 DI2 DI3 / AI2 DI4 / AI1
13 (NO) START FWD STOP (NC) (NO) START REV KPD REF P-20 REF
˄-----------------------------FAST STOP (P-24)---------------------------------------------˄
14 STOP RUN DI2 E-TRIP OK DI2 DI4 PR
0 0 P-20
1 0 P-21
0 1 P-22
1 1 P-23
15 STOP RUN P-23 REF AI1 Fire Mode Analog Input AI1
16 STOP RUN P-23 REF P-21 REF Fire Mode FWD REV
17 STOP RUN DI2 Fire Mode DI2 DI4 PR
0 0 P-20
1 0 P-21
0 1 P-22
1 1 P-23
7.4. Macro Functions - Keypad Mode (P-12 = 1 or 2)
P-15 DI1 DI2 DI3 / AI2 DI4 / AI1
0 1 0 1 0 1 0 1
0 STOP ENABLE - INC SPD - DEC SPD FWD REV
˄------------------ START -----------------˄
1 STOP ENABLE PI Speed Reference
2 STOP ENABLE - INC SPD - DEC SPD KPD REF P-20 REF
˄------------------ START -----------------˄
3 STOP ENABLE - INC SPD E-TRIP OK - DEC SPD
˄---------------------------------------- START --------------------------------------˄
4 STOP ENABLE - INC SPD KPD REF AI1 REF AI1
5 STOP ENABLE FWD REV KPD REF AI1 REF AI1
6 STOP ENABLE FWD REV E-TRIP OK KPD REF P-20 REF
7 STOP RUN FWD STOP RUN REV E-TRIP OK KPD REF P-20 REF
˄-----------FAST STOP (P-24)--------------˄
14 STOP RUN - - E-TRIP OK - -
15 STOP RUN PR REF KPD REF Fire Mode P-23 P-21
16 STOP RUN P-23 REF KPD REF Fire Mode FWD REV
17 STOP RUN KPD REF P-23 REF Fire Mode FWD REV
8,9,10,11,12
, 13
= 0
7.5. Macro Functions - Fieldbus Control Mode (P-12 = 3, 4, 7, 8 or 9)
P-15 DI1 DI2 DI3 / AI2 DI4 / AI1
0 1 0 1 0 1 0 1
0 STOP ENABLE FB REF (Fieldbus Speed Reference, Modbus RTU / CAN / Master-Slave defined by P-12)
1 STOP ENABLE PI Speed Reference
3 STOP ENABLE FB REF P-20 REF E-TRIP OK Analog Input AI1
5 STOP ENABLE FB REF PR REF P-20 P-21 Analog Input AI1
˄------START (P-12 = 3 or 4 Only)--------˄
6 STOP ENABLE FB REF AI1 REF E-TRIP OK Analog Input AI1
˄------START (P-12 = 3 or 4 Only)--------˄
7 STOP ENABLE FB REF KPD REF E-TRIP OK Analog Input AI1
˄------START (P-12 = 3 or 4 Only)--------˄
14 STOP ENABLE - - E-TRIP OK Analog Input AI1
15 STOP ENABLE PR REF FB REF Fire Mode P-23 P-21
16 STOP ENABLE P-23 REF FB REF Fire Mode Analog Input AI1
17 STOP ENABLE FB REF P-23 REF Fire Mode Analog Input AI1
2,4
,8,9,10,11,12
,13
= 0
7.6. Macro Functions - User PI Control Mode (P-12 = 5 or 6)
P-15 DI1 DI2 DI3 / AI2 DI4 / AI1
0 1 0 1 0 1 0 1
0 STOP ENABLE PI REF P-20 REF AI2 AI1
1 STOP ENABLE PI REF AI1 REF AI2 (PI FB) AI1
3, 7 STOP ENABLE PI REF P-20 E-TRIP OK AI1 (PI FB)
4 (NO) START (NC) STOP AI2 (PI FB) AI1
5 (NO) START (NC) STOP PI REF P-20 REF AI1 (PI FB)
6 (NO) START (NC) STOP E-TRIP OK AI1 (PI FB)
8 STOP RUN FWD REV AI2 (PI FB) AI1
14 STOP RUN - - E-TRIP OK AI1 (PI FB)
15 STOP RUN P-23 REF PI REF Fire Mode AI1 (PI FB)
16 STOP RUN P-23 REF P-21 REF Fire Mode AI1 (PI FB)
17 STOP RUN P-21 REF P-23 REF Fire Mode AI1 (PI FB)
2,9,10,11,12
,13
= 0