Installation Manual
Chapter 4 N40475
Page 10
Figure 2 shows the exhaust elbow (1) with water
injection and insulating blanket (3) & (4). The elbow
can be rotated (2) to achieve the optimal position.
Note: The exhaust elbow must have a fall of 10
O
downwards.
If a taller system is required then a dry 90
O
elbow
(not shown) can be used on the turbocharger outlet
with the water injected elbow (1). As both elbows use
a clamp, full articulation can be utilised to suit most
applications
Note: The clamps are to be torqued to 9Nm.
Due consideration must be given to providing exibility
in the exhaust hose, particularly if the engine is
exibly mounted. Where the exhaust hose must pass
through a bulkhead immediately behind the engine it
is preferable that the arrangement shown in gure 3 is
adopted, using rubber bellows (1) to provide exibility.
Note: that the bellows should be in an unstrained
condition when tted, a minimum fall of 5
o
(3) is
required, and that the point of water injection must be
at least 8 inches above the waterline (2).
Note: A single double hump bellows can be used
where space is restricted.
Caution: Movement of the engine on the exible
mounts must not be restricted by the exhaust hose.
Figure 2
Figure 3