Installation Manual
Electrical & Electronic Application And Installation Manual
Production Release Version 1.0
Page 204
Service Tool
Description
J1939
description
Status
SPN
(J1939)
FMI
(J1939)
Event
Code
Engine Action (If
enabled)
Auxiliary
Temperature
Auxiliary
Temperature
#1
Severity L1 441 17 445-1 Warning Lamp
Only
Severity L2 441 18 445-2 Engine % Derate
Severity L3 441 01 445-3 Engine Shutdown
Table 15.8 Auxiliary Temperature Sensor Monitoring
When enabled the engine ECM is able to respond with either an engine
derate or shut down upon receiving a temperature value, which is above a
pre-defined threshold.
15.4.2 Auxiliary Temperature Sensor Configuration
The default condition for this sensor option is ‘uninstalled’. Before any
configuration of the monitoring system for the temperature sensor can take
place this status must be changed using the service tool to ‘Installed’. This
option can be found on the main configuration screen within the service tool.
Once ‘Installed’ the following parameters can be configured;
•
Time delay or ‘debounce’ time before the ECM acts upon the inputted
temperature signal.
•
The Aux Temperature sensor severity level set points can be set.
Table 15.9 Provides details on each of the configurable elements, their
configurable range and default settings.
High Auxiliary Temper
ature Monitoring Configuration
Status
Default
Value
Delay Time (sec)
Set Points
Range
Default
Range
Default
Severity L1 On if
Installed
1 to 120sec 4
0°C to 140°C
105°C
Severity L2 Off 1 to 120sec 4 106°C
Severity L3 Off 1 to 120sec 4 107°C
Table 15.9 Auxiliary Temperature Monitoring Mode Operation Configuration
15.4.3 Auxiliary temperature Sensor Installation
The Perkins auxiliary temperature sensor part number must be used in order
to accurately measure temperature. Third party sensors will not be
compatible with the hardware and software. The auxiliary temperature sensor
is a 0-5V passive analogue sensor with an operating range of –30 to 140°C (-
22 to 248°F). The auxiliary temperature sensor is shown in figure 15.7 and
table 15.10 indicates the components required to connect to the sensor.