If the DUT is a potentiometer type device, disconnect it from the test circuit
and measure the resistance across the track (from V+ to V-).
11.1.4.2 Required Values
If the results obtained from the tests above are in the ranges specified below,
then the device will be compatible with the default values in the ECM.
Test
Parameter
Units
Min
Nominal
Max
1 Output at Min position Volts 0.45 0.6 0.7
2 Output at Min position: forced Volts 0.4 0.6 -
3 Output at Max position Volts 3.8 4 -
4 Output at Max position: forced Volts - 4 4.5
5 IVS switch Closed Voltage Volts 0 0.5 1.2
6 IVS switch Opening Threshold Volts 1.08 1.15 1.22
7 IVS switch Open Voltage Volts 4 10 24
8 IVS switch Closing Threshold Volts 1.08 1.15 1.22
9 Potentiometer Track resistance K Ohms 1 2.5 3
Table 11.1 Analogue Throttle Configuration Parameters
If the results of the tests are not in the range specified in the table above, then
the device will not be compatible with the default settings in the ECM. Contact
the electronic applications team to determine whether it will be possible to
configure the input to meet the device needs.