Accessing the programming routine
The operating mode can be programmed separately for each of the two switching outputs. The operating mode of the switching output (C/Q) is
programmed via push button T1. The operating mode of the analog output is programmed via push button T2.
To access the programming routine for the sensor operating mode, press the push button for 5 seconds.
Programming the output mode
The green LED is now flashing. The number of flashes indicates the output function currently programmed:
Switching output Analog output
1x: Switching point mode 1x: rising slope
2x: Window mode 2x: falling slope
3x: Hysteresis mode 3x: zero point line
4x: Retroreflective sensor mode
1. Briefly press the push button to navigate through the output configurations in succession. Use this method to choose the required output
mode.
2. Press and hold the push button for 2 seconds to save the selection and switch to the programming routine for the output behavior.
Programming the output behavior
The yellow LED is now flashing. The number of flashes indicates the output behavior currently programmed:
Switching output Analog output
1x: NO contact 1x: Current output (4–20 mA)
2x: NC contact 2x: Voltage output (0–10 V)
3x: Deactivated: high impedance
1. Briefly press the push button to navigate through the output behaviors in succession. Use this method to choose the required output function.
2. Press and hold the push button for 2 seconds to save the selection and switch to the programming routine for the sound cone.
Programming the shape of the sound cone
The red LED is now flashing. The number of flashes indicates the sound cone shape currently programmed:
1x: narrow
2x: medium
3x: wide
1. Briefly press the push button to navigate through the different sound cone shapes in succession. Use this method to choose the required
sound cone shape.
2. Press and hold the push button for 2 seconds to return to normal mode.
Note
The last sound cone shape programmed applies for both
outputs in equal measure.
Resetting the sensor to the factory settings
The sensor can be reset to the original factory settings.
1. Disconnect the sensor from the power supply
2. Press and hold one of the push buttons
3. Connect the power supply (yellow and red LEDs flash simultaneously for 5 seconds, followed by the yellow and green LEDs flashing simul-
taneously)
4. Release the push button
The sensor will now function with the original factory settings.
Factory settings
See technical data.
Indicators
The sensor has four LEDs for indicating the status and two buttons for setting parameters.
LED,
green
LED L1, yellow LED L2, yellow LED, red
In normal mode
Error-free operation
Fault (e.g. compressed air)
On
Off
The output status
retains the last
status
The output status
retains the last
status
Off
On
When programming the switching
points or trip values
Object detected
No object detected
Confirmation, programming successful
Warning, programming invalid
Off
Off
Flashes 3x
Off
Flashes
Off
Off
Off
Flashes
Off
Off
Off
Off
Flashes
Off
Flashes 3x
When programming the operating
mode
Programming the output mode
Programming the output behavior
Programming the sound cone
Flashes
Off
Off
Off
Flashes
Off
Off
Flashes
Off
Off
Off
Flashes
L1
L2
T1 T2
L1
L2
LED
green/red
LED yellow LED yellow