Description of Sensor Functions
Programming
The sensor is equipped with two outputs. Two switching points or trip values as well as the output mode, can be programmed for each output.
The shape of the sensor sound cone can also be programmed. These parameters can be configured using two different methods:
- Using the sensor push buttons
- Using the IO-link interface of the sensor. This method requires an IO-link master (e.g. IO-link master01 USB) and the associated software.
The download link is available on the product page for the sensor with the IO link at www.pepperl-fuchs.de
Configuration using the push buttons is described below. To configure the parameters using the sensor IO-link interface, please read the software
description. The processes for configuring the switching points and the sensor operating modes run completely independently and do not influ-
ence one another.
Note:
- The sensor can only be programmed during the first 5 minutes after switching on. This time is extended during the actual programming pro-
cess. The option of programming the sensor is revoked if no programming activities take place for 5 minutes. After this, programming is no
longer possible until the sensor is switched off and on again.
- The programming activities can be canceled at any time without changing the sensor settings. To do so, press and hold the push button for
10 seconds.
Programming the switching point/trip value of the analog characteristic
Note:
Each push button is assigned to a physical output. The switching output (C/Q) is programmed via push button T1. The analog output is program-
med via push button T2.
A flashing red LED during the programming process indicates unreliable object detection. Should this occur, correct the alignment of the object
until the yellow LED L1 or L2 flashes. Only then will the settings be transferred to the sensor memory.
Programming the switching points/trip values using the push button
Programming the near switching point/trip value of the analog characteristic
1. Position the object at the site of the required near switching point or trip value.
2. Press and hold the push button for 2 seconds (yellow LED flashes)
3. Briefly press the push button (green LED flashes 3 times as confirmation). The sensor returns to normal mode.
Programming the far switching point/trip value of the analog characteristic
1. Position the object at the site of the required far switching point or trip value.
2. Press and hold the push button for 2 seconds (yellow LED flashes)
3. Press and hold the push button for 2 seconds (green LED flashes 3 times as confirmation). The sensor returns to normal mode.
Programming the operating modes
The sensor features a 3-stage process for programming the sensor operating modes. You can program the following with this process:
1. Output mode
2. Output behavior of the switching output/analog output
3. The shape of the sound cone
These two stages of the process are programmed in succession. To switch from one programming function to the next, press and hold the push
button for 2 seconds.
Accessories
IO-Link-Master02-USB
IO-Link master, supply via USB port or separate power supply, LED indicators, M12
plug for sensor connection
BF 30
Mounting flange, 30 mm
BF 30-F
Mounting flange with dead stop, 30 mm
BF 5-30
Universal mounting bracket for cylindrical sensors with a diameter of 5 ... 30 mm
V15-W-2M-PVC
Female cordset, M12, 5-pin, PVC cable
UVW90-M30
Ultrasonic -deflector
UVW90-K30
Ultrasonic -deflector
DA5-IU-2K-V
Process control and indication equipment
1 BN
2 WH
3 BU
4 BK
5 GY
Wire colors in accordance with EN 60947-5-2