Functional Description
The sensor may be completely parameterised via two keys on the side panel of the housing. As a special feature provided by
this sensor, the ultrasound beam width may be adapted to the environmental conditions at the place of operation of the sensor.
Specifying the evaluation limits:
The evaluation limits determine the characteristic line and the working range of the analog output.
The A2 evaluation limit is specified via the A2 key, analogous to the description above.
Alternatively, the evaluation limits may also be specified electrically via the learn input. To specify the A1 evaluation limit, the
learn input must be connected to
-U
B
; to specify the A2 evaluation limit, it must be connected to +U
B
. Specified values are saved upon the disconnection from
the learn input.
Evaluation limits may only be specified within the first 5 minutes after Power on. To modify the evaluation limits later, the user
may specify the desired values only after a new Power On.
Proceed as follows to parameterise the output function and the ultrasound beam width:
Press the A1 key during Power on and hold down the key for another second to ensure that the sensor starts the two-step parameterisation of the operating
modes.
Step 1, parameterisation of the output function
The output function parameterised last is displayed. All output functions available may be selected via consecutive, brief strokes
of the A2 key. These strokes are visualised via short flashes of the green LED.
The "Zero point straight line“ setting fixedly specifies the A1 evaluation limit to 0 (see specification of the evaluation limits). The A2 evaluation limit determines
the steepness of the output characteristic line.
Hold down the A1 key for 2 seconds to save the selected output mode, complete the parameterisation and ensure that the sensor returns to normal mode.
If you briefly press the A1 key, Step 2 is entered (parameterisation of the ultrasound beam width).
Step 2, parameterisation of the ultrasound beam width
Via Step 2, the ultrasound beam width may be adapted to the requirements of the corresponding application.
The beam width parameterised last is displayed first. Available beam width settings may be selected via consecutive, brief
strokes of the A2 key. These strokes are visualised via the flash sequence of the red LED.
Hold down the A1 key for 2 seconds to save the selected beam shape, terminate the parameterisation and ensure that the sensor returns to normal mode.
Briefly press the A1 key to return to Step 1 (parameterisation of the output function).
If the parameterisation mode is not terminated within 5 minutes (hold down the A1 key for 2 seconds), the sensor aborts this mode without modifying the
settings.
Specifying the A1 evaluation limit by pressing the A1 key
Holding down the A1key > 2
seconds
The sensor switches to learn mode and the user may
specify the A1 evaluation limit
Position the target object at
the desired distance
The yellow LED of the sensor flashes fast to indicate
that the target object is recognised. The red LED flash-
es if the object is not recognised.
Briefly pressing the A1 key The sensor terminates the specification of the A1 eval-
uation limit and saves it as a non-volatile value. The
specified value is invalid if the object is uncertain (i.e.
the red LED lights up at irregular intervals). The learn
mode is exited.
Operating mode Flash sequence of the green LED A2 key
Rising edge
Falling edge
Zero point straight
line
Beam width Flash sequence of the red LED A2 key
Small beam
Medium beam
Large beam
pause
pause
pause
pause
pause
pause