Mini Limit Switch Series Programming
output and the red LED will stay OFF. If the light received doesn't exceed the maximum level,
perhaps due to a dirty lens, or doesn't fall below the minimum level, perhaps due to a background
reflection, then the red LED will flash and the weak signal output will turn ON. This condition will
continue until the normal light levels are received again by the sensor for one full cycle.
Dynamic Mode of Operation for the Diffused Mode M1K sensors
t
t
t
t
Stability Control
Range
Switching Hysteresis
Input signal level
Switch on point
Switch off point
Switch Output
(Normally Open)
LED Yellow
DUAL-LED
Green - Power
Red - Stability Control
Weak
Signal
Output
Background
Reflection
Poor Target
Reflection
Contamination
Light received
by sensor
Pulse Frequency (S4)
(OFF=Pulse frequency 1, ON=Pulse frequency 2)
Setting two different pulse frequencies for two sensors prevents cross-talk between them
even for side-by-side mounting.
Selectable Switch Output (S5)
(OFF=Normally Open, On=Normally Closed)
Address preset to 00, can be changed via the master or
with a hand-held addressing device.
IO-Code 1
ID-Code 1
Data bits
Bit Function
D0 switch output
D1 weak signal indication (0=on, 1=off)
D2 operational availability
D3 switching frequency, 200Hz*/1.5kHz
†
Parameter bits
Bit Function (1/2)
P0 pulse frequency, 1*/2
P1 switch output, light on*/dark on
P2 pulse lengthener (20ms), off*/on
P3 weak signal indication
†
, dynamic*/static
†
no weak signal indication with 1.5kHz
*default setting
AS-Interface Programming