Datasheet

1
Inductive sensor NBB2-V3-E2-3G-3D
Release date: 2016-11-07 10:13 Date of issue: 2016-11-07 211276_eng.xml
Germany: +49 621 776 4411Pepperl+Fuchs Group
Refer to “General Notes Relating to Pepperl+Fuchs Product Information”.
USA: +1 330 486 0001 Singapore: +65 6779 9091
www.pepperl-fuchs.com fa-info@us.pepperl-fuchs.com fa-info@sg.pepperl-fuchs.com
fa-info@de.pepperl-fuchs.com
Model Number
NBB2-V3-E2-3G-3D
Features
•2 mm flush
•3-wire DC
• ATEX-approval for zone 2 and zone 22
Technical Data
General specifications
Switching function Normally open (NO)
Output type PNP
Rated operating distance s
n
2 mm
Installation flush
Output polarity DC
Assured operating distance s
a
0 ... 1.62 mm
Reduction factor r
Al
0.35
Reduction factor r
Cu
0.2
Reduction factor r
304
0.7
Nominal ratings
Operating voltage U
B
10 ... 30 V DC
Switching frequency f 0 ... 1000 Hz
Reverse polarity protection yes
Short-circuit protection pulsing
Voltage drop U
d
≤ 3 V
Operating current I
L
0 ... 100 mA
Off-state current I
r
0 ... 0.5 mA typ. 0.1 µA at 25 °C
No-load supply current I
0
≤ 15 mA
Switching state indicator LED, yellow
Ambient conditions
Ambient temperature -25 ... 70 °C (-13 ... 158 °F)
Mechanical specifications
Connection type cable PVC , 130 mm
Core cross-section 0.14 mm
2
Housing material PBT
Sensing face PBT
Degree of protection IP67
Cable
Bending radius
> 10 x cable diameter
General information
Use in the hazardous area see instruction manuals
Category
3G; 3D
Compliance with standards and directives
Standard conformity
Standards
EN 60947-5-2:2007
IEC 60947-5-2:2007
Approvals and certificates
UL approval cULus Listed, General Purpose
CSA approval cCSAus Listed, General Purpose
CCC approval CCC approval / marking not required for products rated ≤36 V
Dimensions
Electrical Connection
ø 3
5.5
1010.3
22.2
27.8
16
LED
BN
L+
L-
BK
BU