Inductive sensor NJ5-30GK-S1N-10M
4
Release date: 2019-05-20 08:29 Date of issue: 2019-05-20 250949_eng.xml
Equipment protection level Gb
Type of protection intrinsic safety
CE marking 0102
Certificates
Appropriate type
NJ 5-30GK-S1N...
ATEX certificate
PTB 00 ATEX 2049 X
ATEX marking
¬ II 1G Ex ia IIC T6…T1 Ga
Standards
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx certificate
IECEx PTB 11.0092X
IECEx marking
Ex ia IIC T6...T1 Ga
Standards
IEC 60079-0:2011 , IEC 60079-11:2011
Effective internal capacitance C
i
≤ 100 nF
A cable length of 10 m is considered.
Effective internal inductance L
i
≤ 200 µH
A cable length of 10 m is considered.
Maximum permissible ambient temperature T
amb
Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at U
i
= 16 V , I
i
= 25 mA , P
i
= 34 mW ,
T6 : 73 °C (163.4 °F)
T5 : 88 °C (190.4 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at U
i
= 16 V , I
i
= 25 mA , P
i
= 64 mW ,
T6 : 69 °C (156.2 °F)
T5 : 84 °C (183.2 °F)
T4 : 100 °C (212 °F)
T3 : 100 °C (212 °F)
T2 : 100 °C (212 °F)
T1 : 100 °C (212 °F)
at U
i
= 16 V , I
i
= 52 mA , P
i
= 169 mW ,
T6 : 51 °C (123.8 °F)
T5 : 66 °C (150.8 °F)
T4 : 80 °C (176 °F)
T3 : 80 °C (176 °F)
T2 : 80 °C (176 °F)
T1 : 80 °C (176 °F)
at U
i
= 16 V , I
i
= 76 mA , P
i
= 242 mW ,
T6 : 39 °C (102.2 °F)
T5 : 54 °C (129.2 °F)
T4 : 61 °C (141.8 °F)
T3 : 61 °C (141.8 °F)
T2 : 61 °C (141.8 °F)
T1 : 61 °C (141.8 °F)
Equipment protection level Gc (nA)
Type of protection "n"
CE marking
Certificates
ATEX certificate
PF 15CERT3754 X
ATEX marking
¬ II 3G Ex nA IIC T6 Gc
Standards
EN 60079-0:2012+A11:2013 , EN 60079-15:2010
Possible characteristics maximum operating voltage U
Bmax
, maximum load current I
Lmax
, minimum series resistance R
V
, maximum analog
output voltage U
Amax
, maximum analog output current I
Amax
Maximum permissible ambient temperature T
amb
Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values. :
using an amplifier in accordance with EN 60947-5-6 : 58 °C (136.4 °F)
at U
Bmax
= 9 V , R
V
= 562 Ω : 58 °C (136.4 °F)
Equipment protection level Da
Type of protection intrinsic safety
CE marking 0102
Certificates
Appropriate type
NJ 5-30GK-S1N...
ATEX certificate
PTB 00 ATEX 2049 X
ATEX marking
¬ II 1D Ex ia IIIC T135°C Da
Standards
EN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx certificate
IECEx PTB 11.0092X
IECEx marking
Ex ia IIIC T135°C Da
Standards
IEC 60079-0:2011 , IEC 60079-11:2011
Effective internal capacitance C
i
≤ 100 nF
A cable length of 10 m is considered.
Effective internal inductance L
i
≤ 200 µH
A cable length of 10 m is considered.
Maximum permissible ambient temperature T
amb
Also observe the maximum permissible ambient temperature stated in the general technical data.
Keep to the lower of the two values.
at U
i
= 16 V , I
i
= 25 mA , P
i
= 34 mW : 100 °C (212 °F)
at U
i
= 16 V , I
i
= 25 mA , P
i
= 64 mW : 100 °C (212 °F)
at U
i
= 16 V , I
i
= 52 mA , P
i
= 169 mW : 80 °C (176 °F)
at U
i
= 16 V , I
i
= 76 mA , P
i
= 242 mW : 61 °C (141.8 °F)