User Manual
SMF2-FG Series Media Filter
Operating & Maintenance Manual
PEP Filters • 322 Rolling Hill Road • Mooresville, NC 28117 • 800-243-4583 • www.pepfilters.com
704-662-3133 (Outside USA) Page 14 of 16 Fax 704-662-3155
rev. 01/02
Table 3: Filter Flow Rates @ 20 gpm/ft
2
(13.58 lps/m
2
)
Filter Model
SMF2- FG
Forward Flow
GPM / LPS
Minimum
Backwash Flow
GPM / LPS
Maximum
Backwash
Flow
GPM / LPS
20 43 / 2.7 32 / 2 43 / 2.7
24 63 / 3.97 47 / 3 63 / 3.97
30 98 / 6.2 74 / 4.7 98 / 6.2
36 141 / 8.89 106 / 6.7 141 / 8.89
42 192 / 12.11 144 / 9 192 / 12.11
48 241 / 15.2 180 / 11.4 241 / 15.2
Table 4: Electrical Requirements - Single Phase
PUMP
HP / KW
Voltage 1 φ
60HZ / 50HZ
Full Load Current (Amps)
0.5 / 0.38 110, 208, 220 9.8, 5.0, 4.9
1 / 0.75 110, 208, 220 16, 8.8, 8
1 / 0.75 110, 208, 220 16, 8.8, 8
2 / 1.5 110, 208, 220 24, 13.2, 12