User Manual

INTELLIMASTER Variable Speed Controller User Manual
6
CONTROL PARAMETER SETTING
Parameters Input Range Unit Default
Set Pressure
0.1 ~ 20.0 bar 3.5
10 ~ 300 psi 30
Run Deviation
-3.0 ~ -0.2 bar -0.3
-50 ~ -3 psi -5
Stop Delay 3.0 ~ 999.9 sec 5.0
Restart Delay 0 ~ 9999 sec 0
Shift Time 0 ~ 9999 Min 60
Maximum Runtime 0 ~ 999 Min 0
P 1 ~ 200 - 25
I 1 ~ 200 - 40
D 1 ~ 200 - 40
Low Pressure Alarm [Used] [Not Used] [Used]
Low Pressure Value
0.1 ~ 10.0 bar 0.3
1 ~ 140 psi 5
Low Pressure Stop 0 ~ 999 sec 10
Low Pressure Restart 0 ~ 999 sec 10
Low Pressure Restart
Time
0 ~ 20 Cyle 3
Pressure Unit [bar] [psi] [bar]