INTELLIMASTER Variable Speed Controller User Manual
8
FUNCTION PARAMETER SETTING
Content
Input Range Unit Default
Sensor Range
0.2 ~ 20.0 bar 16.0
10 ~ 300 psi 230
Sensor Offset
-9.9 ~ 9.9 bar 0.0
-99 ~ -99 psi 0
Auto Reset 0 ~ 20 cycle 5
Min. Out Rate 30.00 ~ 70.00 % 50.00
Stop Rate 30.00 ~ 95.00 % 65.00
Motor Direction [Foward] [Backward] - Forward
Low Current Alarm [Used] [Not Used] - Not Used
Low Current Value 0.0 ~ 99.9 A
Depended on
VSD Model
Low Current Stop 1 ~ 999 sec 10