BASIC DESCRIPTION AND OPERATION OF BOOSTER CONTROLLER
Select number of pumps to be operated by Controller.
Timed Pump Rotation by Hours of Operation: Lead pump will rotate
on every start and changes to next lead pump when continuous
Hours of Operation Timed is timed out. Lag pump turns on and off as
called for.
Same Lead Pump for all Starts: Same Lead pump turns on for every
start. If Lead pump is disabled in anyway, Lead Pump will shift to
next available pump. Lag pump turns on and off as needed.
Transducer Failure Settings, when in Auto mode: Select Alarm or
Fault. Alarm allows continued operation when system is in Auto
Mode, will run at Speed entered in Setting. If no flow detected, drives
will stop. Periodic starts will determine if flow is established. Fault will
stop all drives.
Password Setup: When Enabled, enter up to (4) numbers to be
stored as Password/Pin.
Screensaver: When ON, input mins of inactivity (minimum 2mins).
Review Selections. If need adjusting, use Back or Start Basic Setup
Over button. Press Finish when done.