Installation Guide

2
PARAMETER
DESIGNATION
DEFAULT
0‐01
Language
US English
0‐02
Motor Speed Units, RPM or Hz
Hz
0‐03
Regional Settings
North America
1‐03
Torque Characteristics
Auto EnergyOptim VT
1‐23
Motor Frequency
Nameplate
1‐24
Motor Current
Nameplate
1‐25
Motor Speed
Nameplate
3‐03
Maximum Reference
60Hz
3‐41
Ramp Up Time
2 sec.
3‐42
Ramp Down Time
2 sec.
4‐14
Motor High Speed Limit
60Hz
4‐19
Maximum Output Frequency
60.1Hz
4‐12
Motor Speed Low Limit
0Hz
5‐12
Terminal 27
No Operation
8‐01
Control Site
Control Word Only
8‐03
Control Time Out
Limit 3.0 sec.
8‐04
Control Time Out Function
Stop
8‐10
Control Word Profile
FC Profile
8‐30
Protocol
Modbus RTU
8‐31
Addresses
Drive1 = 2, Drive2 = 3, Drive3 = 4, Drive4 = 5
8‐32
FC Port Baud Rate
19200
8‐33
Parity
Even Parity, 1 Stop Bit
8‐42
PCD Write, Configuration:
[0], [1685] FC Port CTW 1
[1], [1686] FC Port Ref 1
8‐43
PCD Read, Configuration:
[0], [1603] Status Word
[1], [1603] Main Actual Valve
[2], [1614] Motor Current
[3], [1618] Motor Thermal
[4], [1500] Operating Hours
[5], [1501] Running Hours
[6], [1610] Power [KW]
[7], [1634] Heatsink Temp
[8], [1502] Kwh Counter
[9], [1692] Warning Word
[10], [1693] Warning Word 2
[11], [1690] Alarm Word
[12], [1691] Alarm Word 2
[13], [1612] Motor Voltage
[14], [1616] Torque (Nm)
8‐50
50 Thru 56
Bus
0‐50
LCP Copy
All To LCP After Drive successfully
programmed
0‐50
LCP Down Load
Download all from LCP Use existing LCP,
download to drive