Modbus Slave Address Table
Booster Communication: Ethernet Modbus TCP IP Slave, Port 502
Data: All packed values stored as most significant byte
Host IP Address:
.
.
.
, Subnet Mask:
.
.
.
Gateway:
.
.
.
Connection: Port 3, RJ45
Booster Communication: Serial Modbus RS 485 Slave, ID 1
COM 2, 9600, 8, N, 1 (1/2 Duplex)
Connection: Port 2, RJ12 on side of PLC Pin 1 (A+), Pin 6 (B‐)
Int
Addr
Function
#
(Hex)
Description
16 ‐bit
Read
Write
1
640
PLC Mode (Off/Auto) 0=Off, 1=Auto
X
X
2
641
Alarm Active ‐ 0=None, 1=Active
X
X
3
642
Maintenance Alarm Active ‐ 0=None, 1=Active
X
X
4
643
Fault Active ‐ 0=None, 1=Active
X
X
5
644
Drive 1 Fault ‐ 0=None, 1=Active
X
X
6
645
Drive 2 Fault ‐ 0=None, 1=Active
X
X
7
646
Drive 3 Fault ‐ 0=None, 1=Active
X
X
8
647
Drive 4 Fault ‐ 0=None, 1=Active
X
X
9
648
Pump 1 Status (ON/OFF) 0=No Operation, 1=In Operation
X
X
10
649
Pump 2 Status (ON/OFF) 0=No Operation, 1=In Operation
X
X
11
64A
Pump 3 Status (ON/OFF) 0=No Operation, 1=In Operation
X
X
12
64B
Pump 4 Status (ON/OFF) 0=No Operation, 1=In Operation
X
X
13
64C
Pump 1 Comm Status (OK/Error) 0=OK, 1=Error ‐ VFD to PLC
X
X
14
64D
Pump 2 Comm Status (OK/Error) 0=OK, 1=Error ‐ VFD to PLC
X
X
15
64E
Pump 3 Comm Status (OK/Error) 0=OK, 1=Error ‐ VFD to PLC
X
X
16
64F
Pump 4 Comm Status (OK/Error) 0=OK, 1=Error ‐ VFD to PLC
X
X
17
650
All Status Bits (1‐16), Most significant byte first
X
X
18
651
VFD 1 Mode ‐ 0=Auto, 1=Local, 2=HMI Manual, 3=Transducer Failure
X
X
19
652
VFD 2 Mode ‐ 0=Auto, 1=Local, 2=HMI Manual, 3=Transducer Failure
X
X
20
653
VFD 3 Mode ‐ 0=Auto, 1=Local 2=HMI Manual, 3=Transducer Failure
X
X
21
654
VFD 4 Mode ‐ 0=Auto, 1=Local 2=HMI Manual, 3=Transducer Failure
X
X
22
655
Discharge PSI (Set Point) – 4 Digits, 1 Dec (999.9 PSI)
X
X
23
656
Discharge PSI (Scaled Transducer Value) – 4 Digits, 1 Dec (999.9 PSI)
X
X
24
657
Flow GPM (Set Point) – 4 Digits (9999 GPM)
X
X
25
658
Flow GPM (Scaled Transducer Value) – 4 Digits (9999 GPM)
X
X
26
659
Suction PSI (Scaled Transducer Value) – 4 Digits, 1 Dec (999.9 PSI)
X
X
27
65A
Drive 1 Speed (99.9 Hz)
X
X
28
65B
Drive 2 Speed (99.9 Hz)
X
X
29
65C
Drive 3 Speed (99.9 Hz)
X
X
30
65D
Drive 4 Speed (99.9 Hz)
X
X
27
65E
Drive 1 KW (99.99 KW)
X
X
28
65F
Drive 2 KW (99.99 KW)
X
X
29
660
Drive 3 KW (99.99 KW)
X
X
30
661
Drive 4 KW (99.99 KW)
X
X
31
662
Discharge PSI (Set Point) – 4 Digits, 1 Dec (999.9 PSI)
X
X
X
32
663
Flow GPM (Set Point) – 4 Digits (9999 GPM)
X
X
X
33
664
PLC Mode (Off/Auto) 0=Off, 1=Auto
X
X
X