Installation Manual

16 C3401M-D (3/09)
WIRING TABLES
Table F describes the recommended maximum distances for 24 VAC applications, which are calculated
with a 10 percent voltage drop. (Ten percent is generally the maximum allowable voltage drop for
AC-powered devices.)
NOTE: Power consumption is 21 VA per unit. Use a power source with a minimum of 21 VA per unit.
Table F. Wiring Distances
Voltage
Wire Gauge
18
(1.0 mm
2
)
16
(1.5 mm
2
)
14
(2.5 mm
2
)
12
(3.5 mm
2
)
24 VAC 215 ft
(97 m)
341 ft
(154 m)
542 ft
(245 m)
863 ft
(391 m)
Table E. Interface Cable Wiring
Pin Color Function
1 ORANGE UTP-
2 WHITE/ORANGE UTP+
3 GREEN RX-
4 WHITE/GREEN RX+
5BLUE TX-
6 WHITE/BLUE TX+
7 NOT USED
8 NOT USED
9BROWN
24 V
10 WHITE/BROWN
24 V
*Cable requirements:
75-ohm impedance
All-copper center conductor
All-copper braided shield with 95% braid
coverage
Table D. Video Coaxial Cable Requirements
Cable Type*
Maximum
Distance
RG59/U 750 ft (229 m)
RG6/U 1,000 ft (305 m)
RG11/U 1,500 ft (457 m)