Installation Manual

14 C3952M-B (5/14)
Connecting Power and Data
CONNECTING POWER
FH-H SERIES ENCLOSURES
The FH-H Series assembly contains a plate separating the high voltage (power) compartment from the low voltage (data) compartment as shown
in Figure 6.
1. Connect the blue neutral wire to the AC LO (NEUT) connector.
2. Connect the brown hot wire to the AC HI (HOT) connector.
3. Connect the ground wire to the ground terminal.
Figure 6. FH-H Series: High Voltage Power Compartment Separated From Low Voltage Compartment
FH-L, FH-M, AND FH-S ENCLOSURES
For FH-L or FH-M Series, you can connect the 24 VAC wires to either of the power connector wires.
For the FH-S Series, you must observe polarity by connecting the neutral wire to the units neutral connector (black wire) and the hot wire to the
unit’s hot wire connector (red wire). Failure to observe wiring polarity might cause damage to the system.
.
Figure 7. FH-L, FH-M, FH-S Series: Power Connection Area for Low Temperature, High Humidity, and 12 VDC Enclosures
WARNING: The FH-S Series is powered by 12 VDC only. Applying high voltage directly to the FH-S Series will damage the housing, void
the warranty, and create an electrocution hazard that can be harmful or fatal. Do not begin wiring until you have fully read and understand
these installation instructions.
AC HI
(HOT)
AC LO
(NEUT)
FG
GROUND