PureFire PFA-1 Interface Adaptor Installation, Operation, and Maintenance Manual
5
PUREFIRE PFA-1 INTERFACE ADAPTER
Table 6 describes the ERROR_NUMBER values for
Lockout Errors. These are errors that require a
manual reset to continue boiler operation. Table 7
describes the ERROR_NUMBER values for Blocking
Errors. Blocking errors are conditions that allow the
boiler to continue operation as soon as the condition
is corrected.
Table 7 shows values for the WARNING_NUMBER
holding register. These conditions primarily concern
the operation of sensors.
If multiple errors are present, the lowest number
error will be communicated.
Table 5
Determination of General Control Status
Control Status
STATE
Value
ERROR_NUMBER
Value
Control is not
Communicating Properly
0x00 0x00
Control is Operating
Correctly with No Errors
Not 0x00 0xFF
Control is Operating
Correctly with Errors
Not 0x00 Not 0xFF
Table 6A
ERROR_NUMBER (Lockout Errors)
Error Number
Error Designation Description
Decimal Hexadecimal
0 0x00 E2PROM_READ_ERROR Internal Software Error
1 0x01 IGNIT_ERROR 3 Consecutive Failed Ignition Attempts
5 0x05 GV_RELAY_ERROR Gas Valve Relay Problems
6 0x06 SAFETY_RELAY_ERROR Internal Control Error
8 0x08 FAN_ERROR Incorrect Fan Speed
9 0x09 RAM_ERROR Internal Control Error
10 0x0A WRONG_EEPROM_SIGNATURE Internal Control Error
11 0x0B RETURN_HIGHER_THEN_SUPPLY Boiler Return Temp. Higher Than Supply
12 0x0C E2PROM_ERROR Internal Control Error
13 0x0D STATE_ERROR Internal Control Error
14 0x0E ROM_ERROR Internal Control Error
15 0x0F AIR_SWITCH_NOT_OPEN Internal Control Error
16 0x10 15MS_XRL_ERROR Internal Control Error
17 0x11 AIR_SWITCH_NOT_CLOSED Internal Control Error
18 0x12 T_MAX_LOCK_ERROR High Temperature Limit Open
19 0x13 STACK_ERROR Internal Control Error
20 0x14 FLAME_OUT_TOO_LATE_ERROR False Flame Detected After Shutdown
21 0x15 FLAME_ERROR_1 False Flame Detected Before Ignition
22 0X16 20MS_XRL_ERROR Internal Control Error
23 0X17 41MS_ERROR Internal Control Error
24 0X18 TOO_MANY_FLAME_FAILURES 3 Consecutive Flame Failures
25 0X19 FLOW_SWITCH_NOT_CLOSED Flow Switch Open / Circulator Off
26 0X1A FLOW_SWITCH_NOT_OPEN Flow Switch Closed / Circulator On
27 0X1B FLAG_BYTE_INTEGRITY_ERROR Internal Control Error
28 0X1C AD_HI_CPL_ERROR Internal Control Error
29 0X1D AD_LO_CPL_ERROR Internal Control Error
30 0X1E REGISTER_ERROR Internal Control Error