ENG • When installing Peerless wall mounts on a concrete wall, the wall must be at least 8” thick with a minimum
compressive strength of 2000 psi.
• When installing Peerless wall mounts on a cinder block wall, the cinder blocks must meet ASTM C-90
specications and have a minimum nominal width of 8”. Do not drill into mortar joints! Be sure to mount in a solid
part of the block, generally 1” (25 mm) minimum from the side of the block. It is suggested that a standard electric
drill on slow setting is used to drill the hole instead of a hammer drill to avoid breaking out the back of the hole
when entering a void or cavity.
• Never attach expansion anchors to concrete or cinder block covered with plaster, drywall or other nishing
material.
WARNING
1b
1b-1
Level cover plate. Mark mounting holes.
1b-2
5/16"
(8mm)
Do not drill into mortar joints.
Drill mounting holes into supporting surface
(2.5" (64 mm) minimum depth required).
2.5"
(64mm)
5/16"
(8mm)